9-3. SELF-DIAGNOSIS ACTION TABLE

Note: Refer to the manual of outdoor unit for the details of display

         such as F, U, and other E.

Error Code

Abnormal point and detection method

Cause

Countermeasure

P1

Room temperature thermistor (TH1)

The unit is in 3-minute resume
prevention mode if short/open of
thermistor is detected. Abnormal if the
unit does not reset normally after 3 min-
utes. (The unit returns to normal opera-
tion, if it has been reset normally.)
Constantly detected during cooling,
drying, and heating operation.
Short: 90
Open: -40

Defective thermistor
characteristics
Contact failure of connector
(CN20) on the indoor controller
board (Insert failure)
Breaking of wire or contact
failure of thermistor wiring
Defective indoor controller
board

Check resistance value of thermistor.
0

• • • • • • • • • •

15.0k

10

• • • • • • • • • • • •

9.6k

20

• • • • • • • • • • • •

6.3k

30

• • • • • • • • • • • •

4.3k

40

• • • • • • • • • • •

3.0k

If you put force on (draw or bend) the lead wire
while measuring resistance value of thermis-
tor, breaking of wire or contact failure can be
detected.

Check contact failure of connector (CN20) on
the indoor controller board. Refer to 9-7.
Turn the power on again and check restart
after inserting connector again.
Check room temperature display on remote
controller.
Replace indoor controller board if there is
abnormal difference with actual room
temperature.

Turn the power off, and on again to operate
after check.

P2

Pipe temperature thermistor/Liquid
(TH2)

The unit is in 3-minute resume
prevention mode if short/open of
thermistor is detected. Abnormal if the
unit does not reset normally after 3 min-
utes. (The unit returns to normal opera-
tion, if it has been reset normally.)
Constantly detected during cooling,
drying, and heating (except defrosting)
operation.
Short: 90
Open: -40

Defective thermistor
characteristics
Contact failure of connector
(CN44) on the indoor controller
board (Insert failure)
Breaking of wire or contact
failure of thermistor wiring
Defective refrigerant circuit is
causing thermistor tempera-
ture of 90
-40
Defective indoor controller
board

Check resistance value of thermistor.

For characteristics, refer to (P1) above.

Check contact failure of connector (CN44) on
the indoor controller board. Refer to 9-7.
Turn the power on and check restart after
inserting connector again.
Check pipe <liquid> temperature with remote
controller in test run mode. If pipe <liquid>
temperature is extremely low (in cooling
mode) or high (in heating mode), refrigerant
circuit may have defect.
Check pipe <liquid> temperature with remote
controller in test run mode. If there is extremely
difference with actual pipe <liquid> temperature,
replace indoor controller board.

Turn the power off, and on again to operate
after check.

P4

Contact failure of drain float switch (CN4F)

Extract when the connector of drain float
switch is disconnected.
(

and

of connector CN4F is not

short-circuited.)
Constantly detected during operation.

Contact failure of connector
(Insert failure)

Defective indoor controller
board

Check contact failure of float switch connec-
tor.
Turn the power on again and check after
inserting connector again.
Operate with connector (CN4F) short-circuited.
Replace indoor controller board if abnormality
reappears.

P5

Drain overflow protection operation

Suspensive abnormality, if drain float

switch is detected to be underwater for
1 minute and 30 seconds continuously
with drain pump on.
Turn off compressor and indoor fan.

Drain pump is abnormal if the condition

above is detected during suspensive
abnormality.

Constantly detected during drain pump

operation.

Malfunction of drain pump
Defective drain
Clogged drain pump
Clogged drain pipe
Defective drain float switch
Catch of drain float switch or
malfunction of moving parts
cause drain float switch to be
detected under water (Switch
On)
Defective indoor-controller
board

Check if drain pump operates.

Check drain function.

Remove drain float switch connector CN4F
and check if it is short (Switch On) with the
moving part of float switch UP, or OPEN with
the moving part of float switch down.
Replace float switch if it is short with the
moving part of float switch down.
Replace indoor controller board if it is short-
circuited between

-

of the drain float

switch connector CN4F and abnormality
reappears.

It is not abnormal if there is no problem about
the above-mentioned

~

Turn the power off, and on again to operate
after check.

OCH501

Содержание Mr.SLIM PCA Series

Страница 1: ... DIAGRAM 13 9 TROUBLESHOOTING 14 10 SPECIAL FUNCTION 28 11 DISASSEMBLY PROCEDURE 31 ON OFF TEMP COOL DRY AUTO FAN HEAT March 2012 NOTE This manual describes only service data of the indoor units RoHS compliant products have G mark on the spec name plate PARTS CATALOG OCB501 Model name indication WIRED REMOTE CONTROLLER Option IR WIRELESS REMOTE CONTROLLER Option Indoor unit Model names Service Ref...

Страница 2: ...42NHA4 PUY A12 18 24 30 36 42NHA4 PUY A12 18 24 30 36 42NHA4 BS PUY A12 18 24 30 36 42NHA4 BS PUZ HA30 36NHA4 PUZ HA30 36NHA4 OCH504 OCB504 PUZ A42NHA5 PUZ A42NHA5 OCH512 OCB512 PUZ A42NHA5 BS PUZ A42NHA5 BS PUY A42NHA5 PUY A42NHA5 PUY A42NHA5 BS PUY A42NHA5 BS Radio frequency interface Wired remote controller IR wireless remote controller RF thermostat Remote controller Optional parts COOL DRY AU...

Страница 3: ...deterio ration of refrigerant oil etc If dirt dust or moisture enters into refrigerant cycle that can cause deterioration of refrigerant oil or malfunction of com pressor If large amount of mineral oil enters that can cause deterio ration of refrigerant oil etc The refrigerant oil applied to flare and flange connections must be ester oil ether oil or alkylbenzene oil in a small amount Make sure th...

Страница 4: ...f syphon stood vertically Refrigerant is charged from liquid phase No Tool name Specifications 1 Gauge manifold Only for R410A Use the existing fitting specifications UNF1 2 Use high tension side pressure of 5 3MPa G or over 2 Charge hose Only for R410A Use pressure performance of 5 09MPa G or over 3 Electronic scale 4 Gas leak detector Use the detector for R134a R407C or R410A 5 Adaptor for rever...

Страница 5: ...indicators The indicator comes on if the corre sponding timer is set Up Down Air Direction indica tor The indicator shows the direc tion of the outcoming airflow One Hour Only indicator Room Temperature display Shows the room temperature The room temperature display range is 46 102 F The display blinks if the temperature is less than 46 F or 102 F or more Louver display Indicates the action of the...

Страница 6: ... in timer operation or when setting timer button Sets any desired room temperature CLOCK display Displays the current time display Displays the order of timer operation display Displays whether timer is on or off Buttons used to set the hour and minute of the current time and timer settings h and min buttons Temperature setting display Indicates the desired temperature setting which is set display...

Страница 7: ...280 50 3 8 680 26 3 4 230 9 1 16 32 71 A A kW F L A min CFM Pa mmAq dB mm in mm in mm in mm in kg lbs Service Ref Power supply phase cycle voltage Max Fuse Size Min Circuit Ampacity External finish Heat exchanger Fan Fan drive No Fan motor output Fan motor Airflow Low Medium2 Medium1 High External static pressure Operation control Thermostat Noise level Low Medium2 Medium1 High Field drain pipe O ...

Страница 8: ... 26 3 4 230 9 1 16 39 86 A A kW F L A min CFM Pa mmAq dB mm in mm in mm in mm in kg lbs Service Ref Power supply phase cycle voltage Max Fuse Size Min Circuit Ampacity External finish Heat exchanger Fan Fan drive No Fan motor output Fan motor Airflow Low Medium2 Medium1 High External static pressure Operation control Thermostat Noise level Low Medium2 Medium1 High Field drain pipe O D Dimensions W...

Страница 9: ...bar NOTCH High Medium1 Medium2 Low SPL dB 41 39 37 35 LINE 90 80 70 60 50 40 30 20 10 63 125 250 500 1000 2000 4000 8000 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE NC 60 NC 50 NC 40 NC 30 NC 20 NC 70 BAND CENTER FREQUENCIES Hz OCTAVE BAND SOUND PRESSURE LEVEL dB 0 dB 0 0002 μbar NOTCH High Medium1 Medium2 Low SPL dB 43 41 39 37 LINE 90 80 70 60 50 40 30 20 10 63 125 250 500 1000 2000 40...

Страница 10: ...be clogged because of dust 8 Ceiling Electrical box 3 5 FRONT VIEW 11 16 18 4 3 4 121 Φ 4 1 5 1 6 Φ 1 2 5 7 1 2 190 3 76 4 7 8 124 18 1 8 461 1 13 16 46 6 9 3 16 233 2 NOTES 1 Use M10 or W3 8 screw for anchor bolt 2 Please be sure when installing the drain pump option parts refrigerant pipe will be only upward DEFROST STAND BY lamp Emergency operation switch Cooling Receiver Operation lamp Emergen...

Страница 11: ...7 7 1 2 190 1 16 1 10 1 4 260 1 16 2 When electrical box is pulled down 2 15 16 75 2 1 1 2 38 7 4 3 3 8 85 3 3 8 86 15 1 4 387 2 Electrical box Air intake 59 3 4 1518 26 3 4 680 18 3 4 476 57 182 85 7 3 16 3 3 8 2 1 4 In case of wireless remote controller and i see sensor Optional Parts Emergency operation switch Heating Operation lamp Receiver Emergency operation switch Cooling DEFROST STAND BY l...

Страница 12: ...LAY DRAIN PUMP SWITCH MODEL SELECTION See table 1 SWITCH CAPACITY CODE See table 2 CONNECTOR EMERGENCY OPERATION FAN MOTOR VANE MOTOR DRAIN PUMP DRAIN FLOAT SWITCH TERMINAL BLOCK INDOOR OUTDOOR CONNECTING LINE TERMINAL BLOCK REMOTE CONTROLLER TRANSMISSION LINE ROOM TEMP THERMISTOR 32ºF 15kΩ 77ºF 5 4kΩ DETECT PIPE TEMP THERMISTOR LIQUID 32ºF 15kΩ 77ºF 5 4kΩ DETECT COND EVA TEMP THERMISTOR 32ºF 15kΩ...

Страница 13: ...thermistor TH5 Room temperature thermistor TH1 Refrigerant flow in cooling Refrigerant flow in heating Strainer 50 Strainer 50 Heat exchanger Refrigerant GAS pipe connection Flare Refrigerant LIQUID pipe connection Flare REFRIGERANT SYSTEM DIAGRAM 8 PCA A24KA4 TH PCA A30KA4 TH PCA A36KA4 TH PCA A42KA5 TH OCH501 ...

Страница 14: ...oubleshooting of problems The trouble is not reoccurring Logged Not logged Consider the temporary defects such as the work of protection devices in the refrigerant circuit including compressor poor connection of wiring noise and etc Re check the symptom and check the installation environment refrigerant amount weather when the trouble occurred matters related to wiring and etc Reset error code log...

Страница 15: ...frigerant address of the indoor unit for the self diagnosis Note Set refrigerant address using the outdoor unit s DIP switch SW1 For more information see the outdoor unit installation manual If an air conditioner error occurs the indoor unit s sensor emits an intermit tent buzzer sound the operation lamp blinks and the error code is output It takes 3 seconds at most for error code to appear The ch...

Страница 16: ...f times IR wireless remote controller Wired remote controller Beeper sounds OPERATION INDICATOR lamp blinks Check code Number of times IR wireless remote controller Wired remote controller 1 P1 Intake sensor error P9 Pipe TH5 sensor error 2 P2 Pipe TH2 sensor error 3 E6 E7 Indoor outdoor unit communication error 4 P4 Float switch connector CN4F open 5 P5 PA Drain pump error Forced compressor stop ...

Страница 17: ...ed Reverse or open phase wiring for the outdoor unit s power terminal block L1 L2 GR Incorrect wiring between indoor and outdoor units incorrect polarity of S1 S2 S3 Remote controller wire short Note Operation is not possible for about 30 seconds after cancellation of function selection Correct operation For description of each LED LED1 2 3 provided on the indoor controller refer to the following ...

Страница 18: ...1 above Check contact failure of connector CN44 on the indoor controller board Refer to 9 7 Turn the power on and check restart after inserting connector again Check pipe liquid temperature with remote controller in test run mode If pipe liquid temperature is extremely low in cooling mode or high in heating mode refrigerant circuit may have defect Check pipe liquid temperature with remote controll...

Страница 19: ...ive Defective outdoor fan control Overcharge of refrigerant Defective refrigerant circuit clogs Bypass circuit of outdoor unit is defective Cooling or drying mode Check clogs of the filter Remove blockage Refer to 9 6 Check outdoor fan motor Check operating condition of refrigerant circuit Heating mode Check clogs of the filter Remove blockage Refer to 9 6 Check outdoor fan motor Check operating c...

Страница 20: ...en the above mentioned problem of are not applied Diagnose remote controllers a When RC OK is displayed remote con trollers have no problem Turn the power off and on again to check If abnormality generates again replace indoor controller board b When RC NG is displayed replace remote controller c When RC E3 or ERC 00 06 is dis played noise may be causing abnormality If the unit is not normal after...

Страница 21: ...mal point and detection method Cause Countermeasure Fb Indoor controller board Abnormal if data cannot be read normally from the nonvolatile memory of the indoor controller board Defective indoor controller board Replace indoor controller board E1 or E2 Remote controller control board Abnormal if data cannot be read nor mally from the nonvolatile memory of the remote controller control board Error...

Страница 22: ...r Normal operation Each connector on vane motor side is disconnected or set ting the fixed vanes by wired remote controller Phenomena Cause Countermeasure 2 Receiver for IR wireless remote controller Weak batteries of IR wireless remote controller Contact failure of connector CNB on IR wireless remote controller board Insert failure Contact failure of connector CN90 on indoor con troller board Ins...

Страница 23: ...control when the remote control does not function it is possible to activate emergency operation by using the indoor unit emergency operation switch SW1 SW2 of the IR wireless signal receiver board However if the indoor unit microprocessor has failed it is necessary to proceed with points 2 and 3 below as in the case of the wired remote controller 2 When you activate emergency operation of the coo...

Страница 24: ... see sensor Option Abnormal Open or short Red Yellow Red Blue Red Orange Red White Connector Normal 300 Measure the resistance between the terminals with a tester At the ambient temperature of 68 F 86 F Abnormal Open or short Red Yellow Red Blue Red Orange Red White Connector Normal 250 Normal Turn on the indoor unit with the black plastic tape on the outside of i see sensor controller board i see...

Страница 25: ...ntact check Contact of fan motor connector CNMF Power supply check Remove the connector CNMF Measure the voltage in the indoor controller circuit board TEST POINT VDC between 1 and 4 of the fan connector VDC DC294 325V TEST POINT VCC between 5 and 4 of the fan connector VCC DC15V Wiring recovery Replace the indoor controller board Replace the fan motor Replace the indoor controller board Replace t...

Страница 26: ...n pump output DP 208 230V AC option CN01 Connect to the Terminal Block TB4 Indoor outdoor connecting line Between and 208 230V AC CNV Vane motor output MV 12V pulse output SWE Emergency operation Jumper wire J41 J42 Pair No setting for IR wireless remote controller FUSE 6 3A 250V CNMF Fan motor DC 294 325V DC15V VCC Voltage between pins of C955 15VDC Same as of CNMF CN44 Pipe temperature thermisto...

Страница 27: ...ble on the left in the table indicates the jumper line is disco nnected There is no jumper JP1 because these models have the cond eva temperature thermistor TH5 Jumper wire Short Open Without TH5 With TH5 Model JP1 For product Spare parts Indoor controller board type JP3 1 2 3 4 5 ON OFF Service board MODELS PCA A24KA4 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 ON OFF PCA A30KA4 ON OFF PCA A36KA4 PCA A42KA5 ON...

Страница 28: ...Outline of functions Main and sub units operate alternately according to the interval of rotation setting w Main and sub unit should be set by refrigerant address Outdoor Dip switch setting Refrigerant address 00 Main unit Refrigerant address 01 Sub unit When error occurs to one unit another unit will start operation Back up function System constraint This function is available only by the groupin...

Страница 29: ... up function No 5 314 Rotation ON Alternating interval 3day and back up function No 6 315 Rotation ON Alternating interval 5day and back up function No 7 316 Rotation ON Alternating interval 7day and back up function No 8 317 Rotation ON Alternating interval 14day and back up function No 9 318 Rotation ON Alternating interval 28day and back up function Setting No Request code Setting contents Init...

Страница 30: ...e button to perform function setting If above setting operations are done correctly Request code number will appear in data display area Example When the 311 of Request code number is set 311 appears on the screen Refererence You can check current request code number setting by setting the request code number 310 or 320 and pressing the button Example When the current setting is Setting No 2 Reque...

Страница 31: ...ectrical cover and remove the electrical cover 4 Remove 2 screws from the electrical box and pull the electrical box downward Temporarily secure the electrical box using 2 hooks in the back of electrical box 5 Disconnect the connectors on the indoor controller board Removing the electrical box 6 Disconnect the wires from the terminal blocks and pull out the electrical box See Photo 2 Removing the ...

Страница 32: ...screw 4 8 PT See Photo 1 3 Remove 2 screws from the electrical cover and remove the electrical cover 4 Remove 2 screws from the electrical box and pull the electrical box downward 5 Temporarily secure the electrical box using 2 hooks in the back of electrical box 6 Remove the lower casing while pressing the 4 catches of the casing right side of the fan motor See Photo 6 7 Loosen the 2 set screws 2...

Страница 33: ...er 4 Remove 2 screws from the electrical box and pull the electrical box downward Temporarily secure the electrical box using 2 hooks in the back of electrical box 5 Remove 2 screws from the left side beam and remove the beam See Photo 9 6 Loosen 2 set screws 2 hexagon set screws of connect ing joint See Photo 5 7 Remove 3 lower casings while pressing each 4 catches of the casing See Photo 6 8 Rem...

Страница 34: ... the right side panel See Figure 3 4 3 Remove the connector of vane motor 4 Remove 2 screws of vane motor cover then remove vane motor Photo 12 Screws Connector Vane motor and cover Photo 13 Under panel fixing screws 9 Removing the drain pan 1 Remove the air intake grille See Figure 1 2 2 Remove the side panel right and left See Figure 3 4 3 Remove the under panel See Photo 13 Remove the screws of...

Страница 35: ...istor TH5 Pipe cover Pipe cover fixing screws Pipe cover fixing screws See Photo 15 Fastener Photo 18 Liquid pipe temperature thermistor TH2 12 Removing the Auto vane 1 Remove the intake grille See Figure 1 2 2 Remove the right side panel See Figure 3 4 3 Remove the vane motor and cover See Photo 12 4 Slide the auto vane to the vane motor side 5 Remove 2 axes from each vane support pushing the van...

Страница 36: ...See Photo 21 8 Remove 3 screws from the heat exchanger and remove the heat exchanger See Photo 22 Caution To avoid falling of the heat exchanger be sure to hold the heat exchanger by hand For safety reasons this procedure must be performed by two persons Photo 21 Pipe band fixing screw Pipe band Heat exchanger fixing screws Heat exchanger Vane Photo 22 Heat exchanger CCopyright 2012 MITSUBISHI ELE...

Страница 37: ...DOOR UNIT ON OFF TEMP COOL DRY AUTO FAN HEAT March 2012 NOTE RoHS compliant products have G mark on the spec name plate Model name indication Indoor unit Model names Service Ref PCA A24KA4 PCA A24KA4 TH PCA A30KA4 PCA A30KA4 TH PCA A36KA4 PCA A36KA4 TH PCA A42KA4 PCA A42KA5 TH WIRED REMOTE CONTROLLER Option IR WIRELESS REMOTE CONTROLLER Option ...

Страница 38: ...2 1 RoHS PARTS LIST STRUCTURAL AND FUNCTIONAL PARTS 1 PCA A24KA4 TH PCA A30KA4 TH PCA A36KA4 TH PCA A42KA5 TH 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 20 21 22 30 16 17 18 19 23 24 25 26 29 31 27 28 OCB501 ...

Страница 39: ...R 1 1 1 1 12 G E17 648 303 VANE MOTOR ASSY 1 1 1 1 MV 13 G E17 648 085 SIDE PANEL R 1 1 1 1 14 G E17 648 042 GUIDE VANE 3 3 G E17 649 042 GUIDE VANE 3 3 15 G E17 664 700 DRAIN PAN 1 1 G E17 666 700 DRAIN PAN 1 1 16 G E17 648 704 JOINT SOCKET 1 1 1 1 17 G E17 648 706 DRAIN SOCKET COVER 1 1 1 1 18 G E17 648 703 DRAIN HOSE COVER 1 1 1 1 19 G E17 648 717 UNDER PANEL 1 1 G E17 649 717 UNDER PANEL 1 1 2...

Страница 40: ...4 STRUCTURAL AND FUNCTIONAL PARTS 2 PCA A24KA4 TH PCA A30KA4 TH PCA A36KA4 TH PCA A42KA5 TH 5 2 3 4 1 6 7 10 11 12 13 14 15 2 2 2 5 8 9 1 11 14 15 RoHS PARTS LIST OCB501 ...

Страница 41: ...0 SIROCCO FAN 2 2 6 G E17 648 334 MOTOR LEG 1 1 1 1 7 G E17 648 300 INDOOR FAN MOTOR 1 1 MF G E17 649 300 INDOOR FAN MOTOR 1 1 MF 8 G E17 648 333 PIECE MOTOR R L 1 1 1 1 9 G E17 648 518 FAN JOINT ASSY 1 1 1 1 10 G E17 648 499 SHAFT FAN 1 1 G E17 649 499 SHAFT FAN 1 1 11 G E17 648 143 GRILLE HINGE 5 5 6 6 12 G E17 648 100 AIR FILTER Small 1 1 13 G E17 649 100 AIR FILTER Large 1 1 2 2 14 G E17 648 1...

Страница 42: ...17 518 308 THERMISTOR ROOM 1 1 TH1 2 G SENSOR COVER 1 1 RG25V835G03 3 G ELECTRICAL BOX 1 1 BH00R345G08 4 G E17 664 447 CONTROLLER BOARD 1 1 I B 5 G E17 516 375 TERMINAL BLOCK 2P 1 2 1 1 TB5 6 G E17 162 375 TERMINAL BLOCK 3P S1 S2 S3 1 1 TB4 7 G E17 648 382 FUSE 6 3A 250VAC 1 1 FUSE 8 G ELECTRICAL BOX COVER 1 BH00R348G11 G ELECTRICAL BOX COVER 1 BH00R348G22 9 G ELECTRICAL BOX COVER 1 1 RG02V755G03 ...

Страница 43: ...7 OCB501 ...

Страница 44: ... ELECTRIC CORPORATION Distributed in Mar 2012 No OCB501 Made in Japan HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN New publication effective Mar 2012 Specifications are subject to change without notice ...

Отзывы: