8
DATA
4
Model
Refrigerant piping length (one way)
1.0
25ft. (std.)
0.954
40ft.
0.923
50ft.
MSH24WN
2) COOLING CAPACITY CORRECTIONS
3) HEATING CAPACITY
(208V/ 230V)
Model
Indoor air
Outdoor intake air WB temperature(˚F)
75
70
65
TC
13.7
14.5
14.9
TPC
1.66
1.61
1.54
TC
17.1
17.7
18.5
TPC
1.95
1.91
1.84
TC
20.4
20.9
21.6
TPC
2.17
2.12
2.06
TC
23.0
23.6
24.3
TPC
2.29
2.23
2.17
TC
23.7
24.3
25.0
TPC
2.32
2.27
2.21
TC
26.9
27.5
28.1
TPC
2.41
2.36
2.32
IDB
(˚F)
15
25
35
43
45
55
MSH24WN
NOTE: 1. IDB : Intake air dry-bulb temperature
TC : Total Capacity (x10
3
Btu/h)
TPC : Total Power Consumption (kW)
2. Above data is for heating operation without any frost.
4-1. PERFORMANCE DATA
1) COOLING CAPACITY
MSH24WN MUH24WN
Model
Indoor air
Outdoor intake air DB temperature(˚F)
71
67
63
TC
27.0
25.5
24.0
SHC
13.4
16.1
18.3
TPC
1.98
1.86
1.78
TC
25.2
23.8
22.2
SHC
12.5
15.0
17.0
TPC
2.16
2.05
1.96
TC
23.7
22.0
20.7
SHC
11.7
13.9
15.8
TPC
2.33
2.22
2.12
TC
22.0
20.5
18.8
SHC
10.9
12.9
14.4
TPC
2.45
2.35
2.26
TC
20.2
18.8
17.2
SHC
10.1
11.9
13.1
TPC
2.55
2.46
2.35
IWB
(˚F)
75
85
95
105
115
MSH24WN
(208V/ 230V)
NOTE 1. IWB : Intake air wet-bulb temperature
TC : Total Capacity (x10
3
Btu/h), SHC : Sensible Heat Capacity (x10
3
Btu/h)
TPC : Total Power Consumption (kW)
2. SHC is based on 80˚F of indoor intake air DB temperature.
OB310--1.qxp 04.1.13 9:47 AM Page 8