5 CHARACTERISTICS
5.5 Inrush currents at power-on of control circuit
113
5
5.5
Inrush currents at power-on of control circuit
A molded-case circuit breaker and magnetic contactor may fail or malfunction due to an inrush current flowing through the
drive unit's power lines (input lines) at power-on. Therefore, use products with the specifications described on the following
page.
Page 123 Molded-case circuit breakers, fuses
When circuit protectors are used, it is recommended that the inertia delay type, which is not tripped by an inrush current, be
used.
400 V class
The following shows the inrush currents (reference data) that will flow when 480 V AC is applied.
Drive unit
Inrush currents (A
0-P
)
Control circuit power supply (L11/L21)
MR-J5D_
16 A (attenuated to approx. 2 A in 30 ms)