4. TROUBLE INDICATION
4.1 Error code
4
TROUBLE INDICATION
This chapter explains the trouble indications of this product.
Always read the instructions before using the equipment.
For the troubleshooting for firmware update, refer to
.
4.1
Error code
If an error occurs, the following error codes and error messages appear.
4.1.1
Communication error with the inverter
NOTE
• If a timeout error occurs, set the FR Configurator2 to the offline mode. Check the connection of the communication cable, etc.,
and remove any error causing condition, then set it to online.
• The parameter list of FR Configurator2 shows the parameters of the latest inverter at the time of the FR Configurator2 upgrade.
(For the upgrade timing of FR Configurator2, refer to
.) The parameters' setting range, initial value, and numbers may
be different before and after a version upgrade (with functions added).
Error code (HEX)
Error message
Possible cause
Countermeasure
0x010A4171
A remote password is set.
A remote password is set for the
intermediate CPU or Ethernet
module.
Delete the remote password set for
the CPU or Ethernet module.
0x010AC201
0x01801006
The specified module does not
exist.
An incorrect module is specified.
Check the module type and model of
the programmable controller in the
system setting window.
0x01808201
A data transmission error
occurred.
Transmission error.
Check the communication
environment.