3.14.5 Firmware update procedure
USB connection
The following procedure is for the connection with one inverter. Inverter parameters are set to initial values. Before update,
download the firmware file from the Mitsubishi Electric FA Global Website.
1.
Start FR Configurator2. (Record the parameter setting values before firmware update by performing parameter
batch read or other functions when the same setting values are to be used after the update.)
2.
Select [Firmware Update Tool] in the [Tool] menu.
3.
In the "Firmware Update Tool" window, select [
] in [Select VFD firmware] to select the firmware file (*.bin). Click
the "Read file" button to read model information.
4.
In the "Firmware Update Tool" window, select [USB] in [Select interface]. The inverters connected to the personal
computer using the USB connector are detected.
5.
Select the inverters whose firmware are to be updated from among the detected inverters. Click the "Update" button.
USB connection
Inverter
Personal computer