1 SERVO PARAMETER DETAILS
1.3 Gain/filter setting servo parameters group ([Pr. PB_ _ ])
41
1
[Pr. PB32_Speed integral compensation after gain switching
(VICB)]
Set the speed integral compensation for when the gain switching is enabled.
When the setting value of this servo parameter is less than "0.1", the setting value of [Pr. PB10 Speed integral compensation]
is applied.
The setting value of this servo parameter is enabled when [Pr. PA08.0 Gain adjustment mode selection] is set to "3" (manual
mode).
[Pr. PB33_Vibration suppression control 1 - Vibration frequency
after gain switching (VRF11B)]
Set the vibration frequency of vibration suppression control 1 for when the gain switching is enabled.
When the setting value of this servo parameter is less than "0.1", the setting value of [Pr. PB19 Vibration suppression control
1 - Vibration frequency] is applied.
This servo parameter is enabled in the following conditions:
• [Pr. PA08.0 Gain adjustment mode selection] is set to "3" (manual mode).
• [Pr. PB02.0 Vibration suppression control 1 - Tuning mode selection] is set to "2" (manual setting).
• "1" (signal (CDP/C_CDP)) is selected in [Pr. PB26.0 Gain switching selection].
Switching gains during driving may cause a shock. Switch the gains after the servo motor has stopped.
[Pr. PB34_Vibration suppression control 1 - Resonance
frequency after gain switching (VRF12B)]
Set the resonance frequency for vibration suppression control 1 for when the gain switching is enabled.
When the setting value of this servo parameter is less than "0.1", the setting value of [Pr. PB20 Vibration suppression control
1 - Resonance frequency] is applied.
This servo parameter is enabled in the following conditions:
• [Pr. PA08.0 Gain adjustment mode selection] is set to "3" (manual mode).
• [Pr. PB02.0 Vibration suppression control 1 - Tuning mode selection] is set to "2" (manual setting).
• "1" (signal (CDP/C_CDP)) is selected in [Pr. PB26.0 Gain switching selection].
Switching gains during driving may cause a shock. Switch the gains after the servo motor has stopped.
[Pr. PB35_Vibration suppression control 1 - Vibration frequency
damping after gain switching (VRF13B)]
Set the damping of the vibration frequency for vibration suppression control 1 for when the gain switching is enabled.
This servo parameter is enabled in the following conditions:
• [Pr. PA08.0 Gain adjustment mode selection] is set to "3" (manual mode).
• [Pr. PB02.0 Vibration suppression control 1 - Tuning mode selection] is set to "2" (manual setting).
• "1" (signal (CDP/C_CDP)) is selected in [Pr. PB26.0 Gain switching selection].
Switching gains during driving may cause a shock. Switch the gains after the servo motor has stopped.
Initial value
Setting range
Ver.
0.0 [ms]
0.0 to 5000.0
A4
Initial value
Setting range
Ver.
0.0 [Hz]
0.0 to 300.0
A4
Initial value
Setting range
Ver.
0.0 [Hz]
0.0 to 300.0
A4
Initial value
Setting range
Ver.
0.00
0.00 to 0.30
A4
Содержание MELSERVO MR-JET-G Series
Страница 1: ...MR JET G User s Manual Parameters MR JET _G MR JET _G N1 Mitsubishi Electric AC Servo System ...
Страница 2: ......
Страница 148: ...146 4 SERVO PARAMETER SETTING METHOD 4 2 Object dictionary MEMO ...
Страница 159: ...6 NETWORK PARAMETER SETTING METHOD 6 1 Engineering tool 157 6 MEMO ...
Страница 163: ......