17 APPLICATION OF FUNCTIONS
17.1 Scale measurement function
541
17
How to use scale measurement function
Selection of scale measurement function
The scale measurement function is set with the combination of basic setting parameters [Pr. PA01] and [Pr. PA22].
■
Operation mode selection
The scale measurement function can be used during semi closed loop system (standard control mode). Set [Pr. PA01] to "_ _
0 _".
■
Scale measurement function selection
Select the scale measurement function. Select "1 _ _ _" (Used in absolute position detection system) or "2 _ _ _" (Used in
incremental system) according to the encoder you use.
Selection of scale measurement encoder communication method and polarity
"Encoder pulse count polarity selection" in [Pr. PC27] is not related to [Pr. PA14 Rotation direction selection].
Make sure to set the parameter according to the relationships between servo motor and linear encoder/rotary
encoder.
The communication method differs depending on the scale measurement encoder type. For the communication method for
using a linear encoder as scale measurement encoder, refer to "Linear Encoder Instruction Manual". Select "Four-wire type"
because there is only four-wire type for synchronous encoder.
Select the cable to be connected to CN2L connector in [Pr. PC26].
Select a polarity of the scale measurement encoder with the following "Encoder pulse count polarity selection" and "Selection
of A/B/Z-phase input interface encoder Z-phase connection judgment function" of [Pr. PC27] as necessary.
Operation mode selection
[Pr. PA01]
1 0
0
Standard control mode
Setting value
0
Operation mode
Servo motor-side
resolution unit
Control unit
Scale measurement function selection
0: Disabled
1: Used in absolute position detection system
2: Used in incremental system
0
0
0
[Pr. PA22]
0 0
[Pr. PC26]
Load-side encoder cable communication method selection
0: Two-wire type
1: Four-wire type
When using a load-side encoder of A/B/Z-phase differential output method, set "0".
Incorrect setting will trigger [AL. 70] and [AL. 71].
Setting "1" while using an MR-J4-_GF_ servo amplifier will trigger [AL. 37].
0