10 SETTING PARAMETERS
10.2 Setting Network Parameter
Routing parameters
Set communication paths for transient transmission between a station in the own network and stations in other networks.
Window
[View]
[Network Parameter]
"CC IE Field Number of Boards Setting" screen
[Routing Parameters] button
Operating procedure
1.
Set the items on the screen.
2.
Click the [End] button.
Item
Description
Target Network No.
Set the target network number. Numbers cannot be overlapped.
Setting range: 1 to 239
Relay Network No.
Set the first relay network number in the path to the target network.
Setting range: 1 to 239
Relay Station No.
Set the first relay station number in the path to the target network.
Setting range: 0 to 120
Condition Setting of Relay/Target
Network
Set whether MELSECNET/10 network is to be used for routing the network.
[Clear] button
Clears all settings.
[Check] button
Checks whether the settings are correct.