13 TROUBLESHOOTING
13.5 List of Error Codes
13.5
List of Error Codes
When an error occurs while the I/O module with diagnostic functions is running, its error code can be checked in the module
diagnostics window of GX Works3. Additionally, Error flag (X10) turns on when an error occurs.
Error codes of the I/O module with diagnostic functions are classified into minor errors and moderate errors.
• Minor error: Error that occurs due to an incorrect setting in programs or parameters (Number in the 1000s + H). Depending
on the error type, a portion that stops operation differs.
• Moderate error: Hardware failure, self-diagnostics error, or error detected by safety output diagnostics (Number in the
2000s or in the 3000s + H). The entire module stops operation.
A minor error can be cleared by turning on and off Error clear request (Y10) after removing the error cause.
A moderate error can be cleared by resetting the remote head module or turning off and on the power after removing the error
cause. If a moderate error occurs, the module remains in safety stop state until the remote head module is reset or the power
is turned off and on.
The following table lists error codes to be stored.
in an error code: Indicates the number of an I/O terminal in which the error has occurred. In accordance with X0 to XF (input
module) or Y0 to YF (output module), a numerical value of 0 to F is assigned.
Error code
Error name
Error description and cause
Action
1100H
Transmission interval monitoring
time range error
A value other than 6 to 3000 is set in
"Transmission interval monitoring time".
Set "Transmission interval monitoring time" within the
range from 6 to 3000.
1110H
LED indication setting on error
condition range error
A value other than 0 to 2 is set in "LED
indication setting on error condition".
Set "LED indication setting on error condition" within
the range from 0 to 2.
112
H
Wiring selection of input range
error
A value other than 0 to 1 is set in "Wiring
selection of input X
".
Set "Wiring selection of input X
" within the range
from 0 to 1.
113
H
Input response time range error
A value other than 0 to 4 is set in "Input
response time X
".
• Set "Input response time X
" within the range from
0 to 4.
• Set "Input response time X
" to a longer time than
the input dark test pulse output time.
Input dark test pulse output time = Input dark test
pulse OFF time
((Number of pulse output for input
dark test
2) - 1)
1140H
Double input discrepancy auto
recovery setting range error
A value other than 0 to 1 is set in "Double input
discrepancy auto recovery setting".
Set "Double input discrepancy auto recovery setting"
within the range from 0 to 1.
115
H
Double input discrepancy
detection time range error
A value other than 1 to 6000 is set in "Double
input discrepancy detection time X
".
Set "Double input discrepancy detection time X
"
within the range from 1 to 6000.
1160H
Input dark test pulse OFF time
range error
A value other than 0 to 2 is set in "Input dark
test pulse OFF time".
Set "Input dark test pulse OFF time" within the range
from 0 to 2.
1170H
Number of pulse output for input
dark test range error
A value other than 0 to 2 is set in "Number of
pulse output for input dark test".
Set "Number of pulse output for input dark test" within
the range from 0 to 2.
118
H
Wiring selection of output range
error
A value other than 0 to 1 is set in "Wiring
selection of output Y
".
Set "Wiring selection of output Y
" within the range
from 0 to 1.
119
H
Output dark test pulse OFF time
range error
A value other than 0 to 2 is set in "Output dark
test pulse OFF time Y
".
Set "Output dark test pulse OFF time Y
" within the
range from 0 to 2.
11A0H
Number of pulse output for output
dark test range error
A value other than 0 to 2 is set in "Number of
pulse output for output dark test".
Set "Number of pulse output for output dark test"
within the range from 0 to 2.
1400H
Double input discrepancy
detection error
The discrepancy of double input was detected.
• Set "Not used" for "Wiring input selection" of an
unused input terminal.
• Check for a terminal with the error using Double
input discrepancy detection state (Un\G1036), and
review and adjust connected devices and wiring.
(
Page 214 Double input discrepancy detection
1401H
Input dark test error
During an input dark test, test pulses were not
detected.
• Set "Not used" for "Wiring input selection" of an
unused input terminal.
• Check for a terminal with the error using Input dark
test error detection state (Un\G1040), and review
and adjust connected devices and wiring.
(