11 PARAMETER SETTINGS
11.1 Basic Settings
185
11
11
PARAMETER SETTINGS
This chapter describes how to set the parameters of the I/O module with diagnostic functions.
11.1
Basic Settings
Setting procedure
Open "Basic setting" of the engineering tool.
1.
Start Module Parameter.
[Navigation window]
[Parameter]
[Module Information]
Target module
[Module Parameter]
[Basic setting]
2.
Double-click on the item to be changed and enter a setting value.
• Item where a value is selected from a drop-down list
Click the [
] button of the item to be set to display a drop-down list. Select an item.
• Item where a value is entered into a text box
Double-click on the item to be set and enter a numerical value.
Transmission interval monitoring time
"Transmission interval monitoring time" of the I/O module with diagnostic functions is the time used for monitoring where the
master station detects an error on safety communications (data transmission from the I/O module with diagnostic functions to
the master station). If the interval of safety communications from the I/O module with diagnostic functions exceeds the time
set in "Transmission interval monitoring time", the master station detects it as disconnection.
For "Transmission interval monitoring time", set the time satisfying both of the following conditions.
• TM
S2cyc
3
• TM
(SCmst
2) + (LS
2)
TM: Transmission interval monitoring time of the I/O module with diagnostic functions
S2cyc: Control cycle time (
Page 126 Performance Specifications)
SCmst: Safety cycle time of the master station (
MELSEC iQ-R CPU Module User's Manual (Application))
LS: Link scan time (
MELSEC iQ-R CC-Link IE Field Network User's Manual (Application))