132
7 PROCEDURES BEFORE OPERATION
5.
Setting parameters on the remote head module side
Set the system parameters, CPU parameters, and module parameters of each module.
• System parameter and CPU parameter setting (
Page 150 Creating a new project (remote head module side), Page
150 Setting parameters on the remote head module side)
• Module parameter setting of each module (
Page 150 Setting parameters on the remote head module side)
6.
Write to the remote head module
Write the configured parameters to the remote head module using the engineering tool. (
MELSEC iQ-R CC-Link IE Field
Network Remote Head Module User's Manual (Startup))
7.
Resetting the remote head module
Use any of the following methods to restart the system on the remote head module side.
• Turning off and on the power
• Resetting the remote head module (
MELSEC iQ-R CC-Link IE Field Network Remote Head Module User's Manual
(Startup))
Procedure on the SIL2 Process CPU side
1.
Powering on the system
In both systems, check the following items and then power on the system.
• The power supply is wired correctly.
• The power supply voltage satisfies the specifications.
• The SIL2 Process CPU is in STOP state.
Power on the system and ensure that the following LEDs turn on.
• Power supply module: POWER LED
• SIL2 Process CPU: READY LED
• SIL2 function module: READY LED
• Redundant function module: RUN LED
• Master/local module: RUN LED
Although the LED status of each module is as follows after this first step, proceed to the next step.
• SIL2 Process CPU: ERROR LED flashing
• SIL2 function module: ERROR LED flashing
• Redundant function module: ERR LED On
• Master/local module: ERR LED On
2.
Creating a project
Start the engineering tool and create a project. (
Page 151 Creating a new project (SIL2 Process CPU side))
3.
Connecting the personal computer and SIL2 Process CPU
On the personal computer on which the engineering tool is installed, start the engineering tool. (
Page 151 Creating a new
Содержание MELSEC iQ-RX40NC6B
Страница 1: ...MELSEC iQ R I O Module With Diagnostic Functions User s Manual Application RX40NC6B RY40PT5B ...
Страница 2: ......
Страница 125: ...4 OVERVIEW 123 4 MEMO ...
Страница 191: ...12 MAINTENANCE AND INSPECTION 189 12 MEMO ...