36 COUNTER/TIMER FUNCTION BLOCKS
36.7 Off Delay Timer
1995
36
36.7
Off Delay Timer
TOF(_E)
These function blocks turn off a signal after the specified period of time.
Setting data
■
Description, type, data type
Processing details
■
Operation processing
1.
Output
• When (s) turns on, (d) turns on.
• When (s) changes from on to off, (d1) turns off after the time that was set by (n). The delay time elapsed after (d1) turns off
is set to (d2).
• Use the long timer to count the elapsed time.
2.
Delay time setting
The valid setting range of (n) is T#1ms to T#2147483ms. Note that the valid setting range will be as follows by changing the
timer limit setting using the engineering tool.
The value at the falling edge (on to off) of (s) is used for the setting value of (n). When the (n) value is changed when (s) is off,
the new value will be enabled at the next falling edge of (s).
• [RnPCPU (redundant)] If these function blocks are used in a program executed in both systems, they do not operate in the standby system when the
redundant system is in backup mode. (
MELSEC iQ-R CPU Module User's Manual (Application))
Ladder, FBD/LD
Structured text
[Without EN/ENO]
[With EN/ENO]
[Without EN/ENO]
Instance name(IN:=s,PT:=n,Q:=d1,ET:=d2);
[With EN/ENO]
Instance name(EN:=en,ENO:=eno,IN:=s,PT:=n,Q:=d1,ET:=d2);
Argument
Description
Type
Data type
EN
Execution condition (TRUE: Executed, FALSE: Not executed)
Input variable
BOOL
s (IN)
Time measurement
Input variable
BOOL
n (PT)
Delay time setting value
Input variable
TIME
ENO
Output status (TRUE: Normal, FALSE: Abnormal or operation stop)
Output variable
BOOL
d1 (Q)
Output
Output variable
BOOL
d2 (ET)
Elapsed time
Output variable
TIME
Minimum value
Maximum value
Identical to the long timer setting value [ms] in the timer limit setting.
Note that if the long timer setting value is smaller than 1ms, the
minimum value will be 1ms.
The time satisfying the following condition is used.
Note that the maximum value is a value that can be included within the range of time
type because the delay time setting value is of time type (32-bit value).
• Delay time setting value [ms]
2147483647 [ms]
Long timer setting value of in
the timer limit setting [ms]
[Example]
• If the long timer setting value is 0.001ms: T#1ms to T#2147483ms
• If the long timer setting value is 1000ms: T#1000ms to T#2147483000ms
RnCPU RnENCPU
RnSFCPU RnSFCPU
RnPCPU
RnPCPU
(Standard)
(Safety)
(Redundant)
(Process)
s
d1
d2
n
EN
ENO
d1
d2
s
n
Содержание MELSEC iQ-R Series
Страница 1: ...MELSEC iQ R Programming Manual Instructions Standard Functions Function Blocks ...
Страница 2: ......
Страница 24: ...22 INDEX 2092 INSTRUCTION INDEX 2093 REVISIONS 2104 WARRANTY 2105 TRADEMARKS 2106 ...
Страница 34: ...32 MEMO ...
Страница 35: ...33 PART 1 PART 1 OVERVIEW This part consists of the following chapter 1 OVERVIEW ...
Страница 68: ...66 1 OVERVIEW 1 5 Precautions on Programming MEMO ...
Страница 204: ...202 5 SEQUENCE INSTRUCTIONS 5 3 Output Instructions Operation error There is no operation error ...
Страница 470: ...468 6 BASIC INSTRUCTIONS 6 6 Data Conversion Instructions Operation error There is no operation error ...
Страница 472: ...470 6 BASIC INSTRUCTIONS 6 6 Data Conversion Instructions Operation error There is no operation error ...
Страница 479: ...6 BASIC INSTRUCTIONS 6 6 Data Conversion Instructions 477 6 Operation error There is no operation error ...
Страница 504: ...502 6 BASIC INSTRUCTIONS 6 7 Data Transfer Instructions Operation error There is no operation error ...
Страница 518: ...516 6 BASIC INSTRUCTIONS 6 7 Data Transfer Instructions Operation error There is no operation error ...
Страница 520: ...518 6 BASIC INSTRUCTIONS 6 7 Data Transfer Instructions Operation error There is no operation error ...
Страница 754: ...752 7 APPLICATION INSTRUCTIONS 7 9 Real Number Instructions Operation error There is no operation error ...
Страница 756: ...754 7 APPLICATION INSTRUCTIONS 7 9 Real Number Instructions Operation error There is no operation error ...
Страница 758: ...756 7 APPLICATION INSTRUCTIONS 7 9 Real Number Instructions Operation error There is no operation error ...
Страница 760: ...758 7 APPLICATION INSTRUCTIONS 7 9 Real Number Instructions Operation error There is no operation error ...
Страница 895: ...7 APPLICATION INSTRUCTIONS 7 16 Ramp Signal Instruction 893 7 Operation error There is no operation error ...
Страница 917: ...7 APPLICATION INSTRUCTIONS 7 20 Data Processing Instructions 915 7 Operation error There is no operation error ...
Страница 919: ...7 APPLICATION INSTRUCTIONS 7 20 Data Processing Instructions 917 7 Operation error There is no operation error ...
Страница 1415: ...13 SFC PROGRAM INSTRUCTIONS 13 1 SFC Control Instructions 1413 13 Operation error There is no operation error ...
Страница 1448: ...1446 14 REDUNDANT SYSTEM INSTRUCTIONS 14 2 Disabling Enabling System Switching MEMO ...
Страница 1795: ...25 TYPE CONVERSION FUNCTIONS 25 1 Converting BOOL to WORD 1793 25 Operation error There is no operation error ...
Страница 1805: ...25 TYPE CONVERSION FUNCTIONS 25 10 Converting WORD to DINT 1803 25 Operation error There is no operation error ...
Страница 1819: ...25 TYPE CONVERSION FUNCTIONS 25 21 Converting INT to DWORD 1817 25 Operation error There is no operation error ...
Страница 1950: ...1948 32 STRING FUNCTIONS 32 2 Extracting String Data From the Left Right Operation error There is no operation error ...
Страница 1972: ...1970 33 TIME DATA TYPE FUNCTIONS 33 4 Division MEMO ...
Страница 2067: ...APPX Appendix 5 PID Control Program Examples 2065 A 252 Set PID control data for loop 2 ...
Страница 2082: ...2080 APPX Appendix 6 Process Control Program Examples 129 Set the default value of the loop tag ...
Страница 2093: ...APPX Appendix 7 List of Loop Tag Memory Areas Used by Process Control Instructions 2091 A MEMO ...
Страница 2109: ......