6 INTER-MODULE SYNCHRONIZATION FUNCTION (SIMULTANEOUS START OF MULTIPLE MODULES)
201
6
6
INTER-MODULE SYNCHRONIZATION
FUNCTION (SIMULTANEOUS START OF
MULTIPLE MODULES)
This function starts pulse output at the same timing of inter-module synchronization cycle after the acceptance of a positioning
start trigger. With this function, positioning controls excluding the manual control start pulse output at the same timing of inter-
module synchronization cycle. After the positioning start, each RD75 operates independently. As well as the normal
positioning control, the positioning can be started at a different timing for each axis.
Before use
• The inter-module synchronization function performs different controls depending on the setting of [Cd.43] Analysis mode
setting. For control details in each setting, refer to the following.
Page 202 Control in Pre-analysis Mode
Page 206 Control in Normal Analysis Mode
• To use the inter-module synchronization function, "Synchronization Setting within the Modules" must be set in "System
Parameter" of the engineering tool in advance. For details on the settings, refer to the following.
MELSEC iQ-R Inter-Module Synchronization Function Reference Manual
• The inter-module synchronization function can be used only when "Operation Mode" of the basic parameter 3 is set to
"Quick Start Mode". Setting "Operation Mode" to "Q Compatible Mode" and turning off to on PLC READY signal [Y0] cause
Q compatible mode setting error (Error code: 18C0H). In this case, RD75 READY signal [X0] does not turn on.
• A dedicated area that is refreshed at the execution of an inter-module synchronous interrupt program (synchronized
refresh-dedicated area) is provided. To check [Md.61] Analysis complete flag, check the following. The area is refreshed at
the same timing of [Md.61] Analysis complete flag of the axis monitor data. The other buffer memory areas used are
refreshed at the same timing of the quick start.
Monitor item
Monitor
value
Stored contents
Buffer memory address
Axis 1
Axis 2
Axis 3
Axis 4
[Md.61]
Analysis complete flag
0, 1
This area stores the start preparation complete state in the
pre-analysis mode.
54000
54001
54002
54003
Содержание MELSEC iQ-R RD75P4
Страница 1: ...MELSEC iQ R Positioning Module User s Manual Application RD75P2 RD75P4 RD75D2 RD75D4 ...
Страница 2: ......
Страница 13: ...11 MEMO ...
Страница 19: ...17 CONTENTS INDEX 588 REVISIONS 592 WARRANTY 593 TRADEMARKS 594 ...
Страница 498: ...496 13 PROGRAMMING 13 2 List of Labels Used ...
Страница 503: ...13 PROGRAMMING 13 4 Program Example 501 13 ...
Страница 511: ...13 PROGRAMMING 13 4 Program Example 509 13 Torque change program Step operation program Skip program ...
Страница 512: ...510 13 PROGRAMMING 13 4 Program Example Teaching program Continuous operation interrupt program ...
Страница 513: ...13 PROGRAMMING 13 4 Program Example 511 13 Target position change program Absolute position restoration program ...
Страница 514: ...512 13 PROGRAMMING 13 4 Program Example Restart program Parameter data initialization program ...
Страница 515: ...13 PROGRAMMING 13 4 Program Example 513 13 Flash ROM write program Error reset program ...
Страница 516: ...514 13 PROGRAMMING 13 4 Program Example Stop program ...
Страница 565: ...APPENDICES Appendix 4 Operation Examples of When the Remote Head Module Is Mounted 563 A ...
Страница 568: ...566 APPENDICES Appendix 4 Operation Examples of When the Remote Head Module Is Mounted Common program ...
Страница 584: ...582 APPENDICES Appendix 4 Operation Examples of When the Remote Head Module Is Mounted Restart program ...
Страница 587: ...APPENDICES Appendix 4 Operation Examples of When the Remote Head Module Is Mounted 585 A Stop program ...
Страница 597: ......