36 PROCEDURE FOR STARTING UP A SYSTEM USING THE SIL2 PROCESS CPU
36.2 Wiring
597
36
36.2
Wiring
Wiring the redundant function modules
This section describes how to wire the redundant function modules.
Wiring method
Connect the tracking cables from the OUT connector of a redundant function module to the IN connector of the other
redundant function module.
For the specifications of the tracking cables connected to redundant function modules, refer to the following.
MELSEC iQ-R CPU Module User's Manual (Startup)
Connecting/disconnecting tracking cables
■
Connection procedure
1.
Pay attention to the direction of a tracking cable connector and insert the cable to a redundant function module until it
clicks. A redundant function module has one IN connector and one OUT connector. Connect the IN connector of the
system A and the OUT connector of the system B with a tracking cable and connect the OUT connector of the system A
and the IN connector of the system B.
2.
Pull each cable lightly and check that it has been connected securely.
■
Disconnection procedure
1.
Disconnect the tracking cables while pressing the connector hook.
Precautions
• There are restrictions on the cable bending radius. For details, refer to the specifications of the tracking cables used.
• Place the cables in a duct or clamp them. If not, a dangling cable may swing or inadvertently be pulled, resulting in damage
to the module or cables or malfunction due to poor contact.
• When connecting tracking cables, pay attention not to touch optical fiber cores of the connectors on the cables and module
sides and prevent dirt and dust from adhering to them. If oil on hands, dirt, and dust adhere to the optical fiber cores, the
transmission loss increases and tracking may not work properly.
• Hold the connector of the tracking cables to connect or disconnect the cable. Pulling the cable connected to the module
may result in malfunction or damage to the module or cable or malfunction due to poor contact.
IN
OUT
IN
OUT
Содержание MELSEC iQ-R-R00CPU
Страница 2: ......
Страница 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Страница 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Страница 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Страница 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Страница 524: ...522 30 MAINTENANCE AND INSPECTION FOR A REDUNDANT SYSTEM 30 1 Module Replacement in the Redundant System MEMO ...
Страница 1009: ...APPX Appendix 14 List of Available SQL Commands for CPU Module Database Access Function 1007 A MEMO ...
Страница 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Страница 1027: ......