11 DATA LOGGING FUNCTION
11.10 Setting Behavior at the Time of Transition to RUN
203
11
11.10
Setting Behavior at the Time of Transition to RUN
After the data logging settings are registered by the start operation of data logging, set the behavior of data logging when the
following user operations to switch the operating status of the CPU module to RUN are performed (transition to RUN). (
Page 981 Movement)
• Powering off and on and switching the operating status to RUN
• Resetting and switching the operating status to RUN
• Switching the operating status from STOP to RUN
The logging operation can be set individually for each setting number (1 to 10).
Behavior at the time of a transition to RUN
The behavior can be selected from the following.
■
Auto start
The data logging automatically starts after the user operation of starting data logging in CPU Module Logging Configuration
Tool and switching the operating status of the CPU module to RUN.
[Online]
[Logging Status and Operation]
■
Start by user operation
The data logging status becomes "Start waiting (no collection)" after the user operation of starting data logging in CPU Module
Logging Configuration Tool and switching the operating status of the CPU module to RUN. To start data logging, operate CPU
Module Logging Configuration Tool to start data logging again.
[Online]
[Logging Status and Operation]
When the auto logging is used, the behavior of the data logging is always "Auto Start", even if the behavior at
transition to RUN is set to "Start by User Operation". (
Data logging behavior that occurs after operating status of CPU module has changed
Data logging does not continue when the operating state of the CPU module changes from RUN to STOP or PAUSE after it
has been started. The data logging status changes to "RUN waiting (no collection)" and data collection is stopped.
Содержание MELSEC iQ-R-R00CPU
Страница 2: ......
Страница 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Страница 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Страница 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Страница 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Страница 524: ...522 30 MAINTENANCE AND INSPECTION FOR A REDUNDANT SYSTEM 30 1 Module Replacement in the Redundant System MEMO ...
Страница 1009: ...APPX Appendix 14 List of Available SQL Commands for CPU Module Database Access Function 1007 A MEMO ...
Страница 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Страница 1027: ......