174
11 DATA LOGGING FUNCTION
11.2 Data Collection Conditions
Data collection during the END processing after specified time interval
This option causes data collection to be performed at the timing of the END processing rather than during the course of
program execution. Ensure that the "Scan time" is less than "Time specification". If the scan time is longer than the specified
time and the collection interval or the collection timing occurs more than once during the same scan, data is collected only
once during the END processing. Data collection is performed on a scan by scan basis, which is the same behavior as when
"Each scan" is used.
Ex.
10 milliseconds (10ms)
Interrupt occurrence
Data are collected at specified time interval after the execution of an interrupt program. The time interval is specified by
"Interrupt cycle specified sampling intervals"
"Interval". Interrupt pointers which can be specified are I28 to I31, I44, I45, I48,
and I49.
Ex.
When multiple CPU synchronous interrupt (I45) is used (multiple CPU synchronous interrupt is set to 0.22 milliseconds
(0.22ms) and interval to 3):
Since data collection is performed at the timing of the execution of the interrupt program, data is collected only
when all of the following conditions are met:
• The specified interrupt meets the operating condition.
• The specified interrupt pointer exists in the program.
• The current state is an EI state and the interrupt mask of the interrupt pointer has been reset.
0
END
0
END
0
END
0
END
0
END
10ms
10ms
10ms
Program
END processing
Sampling
END processing
END processing
Sampling
END processing
END processing
Set time
1 scan
0.22ms
0.22ms
0.22ms
0.22ms
0.22ms
0.22ms
0.22ms
Sampling
Interrupt
program
execution
Interrupt
Sampling
Interrupt
program
execution
Interrupt
Interrupt
program
execution
Interrupt
Interrupt
program
execution
Interrupt
Sampling
Interrupt
program
execution
Interrupt
Interrupt
program
execution
Interrupt
Interrupt
program
execution
Interrupt
Fixed scan
communication
cycle
Содержание MELSEC iQ-R-R00CPU
Страница 2: ......
Страница 151: ...9 MONITOR FUNCTION 9 1 Real Time Monitor Function 149 9 MEMO ...
Страница 323: ...18 SEQUENCE SCAN SYNCHRONIZATION SAMPLING FUNCTION 321 18 MEMO ...
Страница 330: ...328 20 ROUTING SETTING 20 3 Precautions MEMO ...
Страница 423: ...26 BASIC CONCEPT 26 8 State Transition of the Redundant System 421 26 MEMO ...
Страница 524: ...522 30 MAINTENANCE AND INSPECTION FOR A REDUNDANT SYSTEM 30 1 Module Replacement in the Redundant System MEMO ...
Страница 1009: ...APPX Appendix 14 List of Available SQL Commands for CPU Module Database Access Function 1007 A MEMO ...
Страница 1014: ...1012 APPX Appendix 15 Added and Enhanced Functions MEMO ...
Страница 1027: ......