![Mitsubishi Electric MELSEC iQ-R CC-Link IE TSN Скачать руководство пользователя страница 33](http://html.mh-extra.com/html/mitsubishi-electric/melsec-iq-r-cc-link-ie-tsn/melsec-iq-r-cc-link-ie-tsn_user-manual_1811879033.webp)
1 FUNCTIONS
1.1 Cyclic Transmission
31
1
Direct access to link devices
The corresponding data is directly read or written from/to link devices of the RJ71GN11-T2 using the program.
Specify a link device as the link direct device (J
\
) for direct access.
The link special relay (SB) and link special register (SW) can be set using module label. (
Specification method
Specify the network number and the link devices of the RJ71GN11-T2 for reading or writing data.
Ex.
(1)
Network number: 1 to 239
(2)
Remote input (RX): X0 to X3FFF
Remote output (RY): Y0 to Y3FFF
Remote register (RWw): W0 to W1FFF
Remote register (RWr): W2000 to W3FFF
Link relay (LB): B0 to B7FFF
Link register (LW): W4000 to W7FFF
Link special relay (SB): SB0 to SBFFF
Link special register (SW): SW0 to SWFFF
J
(1) (2)
\
RCPU
X
Y
W
B
W
No.2
RX
RY
RWr
RWw
RX
RY
RWr
RWw
LB
LB
LW
LW
No.0
LB
LB
LW
LW
RX0
RY0
RWw0
RWr100
LB0
LB100
LW200
LW300
J1\Y0
MOV K20 J1\W0
= J1\W2100 K300
J1\B100
J1\B0
MOV K20 J1\W4200
= J1\W4300 K300
J1\X0
Содержание MELSEC iQ-R CC-Link IE TSN
Страница 1: ...MELSEC iQ R CC Link IE TSN User s Manual Application RJ71GN11 T2 ...
Страница 2: ......
Страница 160: ...158 3 PROGRAMMING 3 3 Communication Example of Safety Communication Master station station No 0 ...
Страница 323: ...APPX Appendix 10 Added and Enhanced Functions 321 A MEMO ...
Страница 325: ...I 323 MEMO ...
Страница 329: ......