![Mitsubishi Electric MELSEC iQ-R C R12CCPU-V Скачать руководство пользователя страница 148](http://html.mh-extra.com/html/mitsubishi-electric/melsec-iq-r-c-r12ccpu-v/melsec-iq-r-c-r12ccpu-v_user-manual_239137148.webp)
146
7 CC-Link IE Field Network Basic FUNCTION
7.5 Processing Time
Transmission delay time
A transmission delay time includes an input transmission delay time and an output transmission delay time.
Input transmission delay time
The input transmission delay time indicates the following time.
• Time between when a signal (RX) is input to a slave station and when a device of the master station turns ON or OFF
• Time between data (RWr) is input to a slave station and when the data is stored to the device of the master station
■
Calculation formula for input transmission delay time
• Input transmission delay time (maximum) = (Ls
×
2) + SS [ms]
Output transmission delay time
The output transmission delay time indicates the following time.
• Time between when a device of the master station turns ON or OFF and when the output (RY) of a slave station turns ON
or OFF
• Time between when data is set to a device of the master station and when the data (RWw) is output to a slave station
■
Calculation formula for output transmission delay time
• Output transmission delay time (maximum) = Ls + SS [ms]
Item
Description
Ls
Link scan time [ms]
SS
Processing time required for the slave station to reflect the input [ms]
(
Manual for the slave station used)
Item
Description
Ls
Link scan time [ms]
SS
Processing time required for the slave station to reflect the output [ms]
(
Manual for the slave station used)
Содержание MELSEC iQ-R C R12CCPU-V
Страница 1: ...MELSEC iQ R C Controller Module User s Manual Application R12CCPU V ...
Страница 2: ......
Страница 23: ...1 EXECUTING PROGRAMS 1 3 I O Access Timing 21 1 MEMO ...
Страница 32: ...30 3 MEMORY CONFIGURATION OF C Controller Module 3 4 Files MEMO ...
Страница 257: ...I 255 MEMO ...
Страница 261: ......