![Mitsubishi Electric MELSEC iQ-F Скачать руководство пользователя страница 10](http://html.mh-extra.com/html/mitsubishi-electric/melsec-iq-f/melsec-iq-f_manual_239102010.webp)
8
2 POSITIONING MODULE FB
2.1 M+FX5PG_SetPositioningData
Error code
Timing chart of I/O signals
[For normal completion]
[For error completion]
Restrictions or precautions
• This FB does not include the error recovery processing. Program the error recovery processing separately in accordance
with the required system operation.
• This FB cannot be used in an interrupt program.
• Do not use this FB in programs that are executed only once, such as a subroutine program or FOR-NEXT loop, because
i_bEN (Execution command) cannot be turned off and the normal operation cannot be acquired. Always use this FB in
programs that can turn off i_bEN (Execution command).
• When this FB is used twice or more, precaution must be taken to avoid duplication of the target axis.
• Every input must be provided with a value for proper FB operation.
• The pulse output mode and external input/output signal logic, etc. must be set according to the connected devices and
system before operating the positioning module. Set the GX Works3 module parameters according to the application. Refer
to the
MELSEC iQ-F FX5 User's Manual (Positioning Control - Intelligent function module) for details on setting the
module parameters.
Error code (hexadecimal)
Description
Action
100
The set value of i_uAxis (Target axis) is out of the range.
The target axis is not within the range of 1 to 4.
Try again after checking the setting.
101
The set value of i_uDataNo (Positioning data No.) is out of the
range.
The positioning data No. is not within the range of 1 to 600.
Try again after checking the setting.
Item
Description
i_bEN
o_bENO
o_bOK
o_bErr
o_uErrId
0
Write
Unexecuted
Unexecuted
Positioning data setting write
processing
o_bENO
o_bOK
o_bErr
o_uErrId
i_bEN
0
Error code
0
Unexecuted
Positioning data setting write
processing