6 WIRING
6.7 Examples of Wiring for Various Uses
115
6
High-speed counter
Examples of wiring for high-speed counters are shown below.
When capturing pulses of a response frequency of 50 to 100 kHz, refer to
Page 94 In the case of capturing high-speed
pulses.
For details on the high-speed counters, refer to
MELSEC iQ-F FX5 User's Manual (Application).
For the programs, refer to
MELSEC iQ-F FX5 Programming Manual (Instructions, Standard Functions/Function Blocks).
1-phase 1-input (S/W)
The wiring examples in this section use the following settings. When settings other than those in the table are used, use the
examples shown in the following figures as references for wiring.
The settings of the high-speed counters are set by using the parameter settings of the engineering tool.
For details, refer to
MELSEC iQ-F FX5 User's Manual (Application).
■
Example of wiring
*1 The grounding resistance should be 100
Ω
or less.
CH to be used
Pulse input mode
External preset input External enable input Operation mode
CH1 (CPU module)
1-phase 1-input (S/W)
Invalid
Invalid
Normal mode
1.5 k
In the case of sink wiring
S/S
L
N
24V
0V
24V
Rotary encoder
Class D grounding
*1
Fuse
24 V DC
• NPN open collector transistor output rotary encoder
0V
X0
A phase
B phase
Z phase
FX5UJ-
40MT/ES
1.5 k
24 V DC
In the case of source wiring
S/S
L
N
24V
0V
24V
Rotary encoder
• PNP open collector transistor output rotary encoder
0V
X0
A phase
B phase
Z phase
FX5UJ-
40MT/ESS
Class D grounding
*1
Fuse