6 WIRING
6.6 Output Wiring
99
6
6.6
Output Wiring
The output wiring of the CPU module, I/O modules, and terminal modules is explained below.
Relay output
For output specifications of the CPU module, refer to
Page 31 Output Specifications.
For output specifications of the I/O modules, refer to
Page 152 Output specifications.
For output specifications of the terminal modules, refer to
Page 170 Output specifications.
Product life of relay output contacts
The product life of relay output contacts varies considerably depending on the load type used.
Note that loads generating reverse electromotive force or rush current may cause poor contact or welding of contacts which
may lead to considerable reduction of the contact product life.
■
Inductive load
Inductive loads generate large reverse electromotive force between contacts at shutdown, which may cause arc discharge. At
a fixed current consumption, as the power factor (phase between current and voltage) gets smaller, the arc energy gets larger.
The following table shows the standard life of contacts used for inductive loads, such as contactors and solenoid valves.
The following table shows the approximate life of a relay based on the results of an operation life test.
• Test condition: 1 sec. ON/1 sec. OFF
The product life of relay contacts becomes considerably shorter than the above conditions when the rush overcurrent is shut
down.
Please refer to the following measures regarding the inductive load.
Page 101 Contact protection circuit for inductive loads
Some types of inductive loads generate rush current 5 to 15 times the stationary current at activation. Make sure that the rush
current does not exceed the current corresponding to the maximum specified resistance load.
■
Lamp load
Lamp loads generally generate rush current 10 to 15 times the stationary current. Make sure that the rush current does not
exceed the current corresponding to the maximum specified resistance load.
Model
Inductive load
Standard life
CPU module, FX5-
EYR/ES, FX5-32ER/ES, FX5-16ER/ES,
FX5-C16EYR/D-TS
20 VA
500,000 times
Terminal module
35 VA
Load capacity
Contact life
■
CPU module, FX5-
EYR/ES, FX5-32ER/ES, FX5-16ER/ES, FX5-C16EYR/D-TS
20 VA
0.2 A/100 V AC
3,000,000 times
0.1 A/200 V AC
35 VA
0.35 A/100 V AC
1,000,000 times
0.17 A/200 V AC
80 VA
0.8 A/100 V AC
200,000 times
0.4 A/200 V AC
■
Terminal module
35 VA
0.35 A/100 V AC
3,000,000 times
0.17 A/200 V AC
80 VA
0.8 A/100 V AC
1,000,000 times
0.4 A/200 V AC
120 VA
1.2 A/100 V AC
200,000 times
0.6 A/200 V AC