FX2N-32DP-IF Profibus-DP Interface Unit
Specifications 3
3-3
3.3
Performance Specifications
Table 3.3: Performance Specifications
Items
Specifications
Maximum Number of Controllable
I/O Points
Maximum 256 points (see section 1.3)
Transmission data
(Exchange data length)
Max.200 bytes, total of sent and received during one bus cycle.
(input: Max. 200 bytes, output: Max. 200 bytes)
Transmission Type
Bus network
Port
9 pin D-SUB
Port for Profibus-DP network
8 pin mini DIN
Port for FX-20P-E or personal computer (MELSEC MEDOC
PLUS)
Supported Baud
Rates (bps) and
Bus Length
9.6k, 19.2k,
45.45k, 93.75k
1,200 m (3,937')
187.5k
1,000 m (3,281')
500k
400 m (1,312')
1.5M
200 m (656')
3M, 6M, 12M
100 m (328')
LED Indicators
POWER LED
ON when power is supplied.
RUN LED
ON when 32DP-IF is exchanging data with extension I/O blocks/
units and special function blocks.
BF LED
ON when a communication error is detected. (No data exchange)
DIA LED
ON when notice of diagnostic data is detected.
Содержание MELSEC FX2N-32DP-IF
Страница 1: ...HARDWARE MANUAL FX2N 32DP IF Profibus DP Interface Unit ...
Страница 4: ...FX2N 32DP IF Profibus DP Interface Unit ii ...
Страница 8: ...FX2N 32DP IF Profibus DP Interface Unit vi ...
Страница 20: ...FX2N 32DP IF Profibus DP Interface Unit Introduction 1 1 10 MEMO ...
Страница 22: ...FX2N 32DP IF Profibus DP Interface Unit Mounting and Wiring 2 2 2 Figure 2 2 Mounting Arrangement ...
Страница 40: ...FX2N 32DP IF Profibus DP Interface Unit Specifications 3 3 4 MEMO ...
Страница 46: ...FX2N 32DP IF Profibus DP Interface Unit Diagnostics 5 5 4 MEMO ...
Страница 53: ......