Appendix 2 List of Error Codes
List of error codes
This section shows the codes for errors that occur in this product.
Codes of errors detected by the self-diagnosis function (1000H to 3FFFH)
The following table shows the codes of errors detected by the self-diagnosis function of this product.
Error code
Error name
Description
Corrective action
1000H
Power interruption
• A momentary power failure has occurred.
• The power supply has been shut OFF.
• While turning power on, the CFast card
was inserted or removed.
• Take measures to reduce noise.
• While turning power on, do not insert or
remove the CFast card.
• Reset the system. If the same error is
displayed again, this may indicate a
hardware fault. Consult your local
Mitsubishi representative.
1080H
Internal storage write count exceeded
The number of writes to the internal storage
(user drive and system drive) exceeded
10,000. (Number of writes > 10,000)
Exchange the MELIPC main module.
1090H
Battery error
• Battery voltage has dropped below
specified values.
• The battery lead connector is not
inserted.
• The battery lead connector is not properly
inserted.
• Replace the battery.
• Check the insertion of the battery lead
connector. If it is loose, securely connect
the connector.
1120H
SNTP clock setting error
Time setting failed when the power supply
of this product was turned ON or this
product was reset.
• Check if the setting of time setting
function is correct.
• Check if the specified SNTP server is
operating normally and there is no failure
on the network accessing the SNTP
server computer.
112EH
Connection establishment failed
A connection could not be established in the
open processing.
• Check the operation of the target device.
• Check if the open processing has been
performed in the target device.
• Review the port number of the module, IP
address/port number of the target device,
opening method, and the number of
connections.
• When the firewall is set in the target
device, check if the access is permitted.
• Check if the Ethernet cable is
disconnected.
• Check and correct the external device
configuration.
1165H
UDP/IP send failed
Data was not sent correctly with UDP/IP.
• Check the settings for connection with the
target device.
• Check the operation of the target device
or switching hub.
• Since there may be congestion of packets
on the line, send data after a certain
period of time.
• Check if the connection cable is
disconnected.
• Check that there is no connection failure
with the switching hub.
1166H
TCP/IP send failed
Data was not sent correctly with TCP/IP.
• Check the settings for connection with the
target device.
• Check the operation of the target device
or switching hub.
• Since there may be congestion of packets
on the line, send data after a certain
period of time.
• Check if the connection cable is
disconnected.
• Check that there is no connection failure
with the switching hub.
1200H
CC-Link IE Field Network function
moderate error
A moderate error has been detected in the
CC-Link IE Field Network function.
Check with the generated error in the CC-
Link IE Field Network function, and remove
errors generating faults.
Содержание MELIPC MI5000 Series
Страница 1: ...MELIPC MI5000 Series User s Manual Application MI5122 VW ...
Страница 2: ......
Страница 18: ...16 MEMO ...
Страница 22: ...20 1 DIAGNOSTIC AND MAINTENANCE FUNCTIONS 1 1 Watchdog Timer WDT Function MEMO ...
Страница 42: ...40 5 iQSS FUNCTION MEMO ...
Страница 146: ...144 11 SECURITY FUNCTION 11 3 IP Filter Function MEMO ...
Страница 148: ...146 12 MELSOFT PRODUCT AND GOT CONNECTION FUNCTION 12 1 Connection Method MEMO ...
Страница 150: ...148 13 SYSTEM COUNT FUNCTION MEMO ...
Страница 152: ...150 14 TIMER EVENT FUNCTION MEMO ...
Страница 160: ...158 15 OS LINKING FUNCTIONS 15 3 Inter OS Event Notification Function MEMO ...
Страница 162: ...160 16 SERIAL INTERFACE SWITCHING FUNCTION MEMO ...
Страница 165: ...17 BASIC PARAMETERS 17 1 Basic Parameter List 163 17 Operation related setting Window ...
Страница 170: ...168 17 BASIC PARAMETERS 17 1 Basic Parameter List RAS setting Window ...
Страница 174: ...172 17 BASIC PARAMETERS 17 1 Basic Parameter List External device connection settings Window ...
Страница 177: ...17 BASIC PARAMETERS 17 1 Basic Parameter List 175 17 External device connection applicable settings Window ...
Страница 313: ...APPX Appendix 10 List of VxWorks Components 311 A MEMO ...
Страница 315: ...I 313 MEMO ...
Страница 319: ......