Appendix 1 Troubleshooting by Symptom
POWER LED of the power supply module turns off
Check the following items.
If there are no errors in power supply module wiring and input voltage, the power supply unit may have reached the end of its
operating life or there is a hardware fault. Replace it with a new power supply module.
The MAIN LED is on, flashing, or off
Check the following items.
If the VX RDY LED is not lit
Check item
Corrective action
Is power supply module wiring correct?
Wire the power supply module correctly.
Is the input voltage within specifications?
Change the input voltage to within specifications.
Check item
Corrective action
Is the off-line mode status displayed on the dot matrix LED?
After offline mode operation is complete, turn the product power supply OFF.
Is the VX RDY LED off and the MAIN ERR LED on?
• System watchdog timer error occurred.
• Handle in accordance with the system watchdog timer error code (3E41H).
If the same phenomenon remains after these measures, this may indicate a
hardware fault with the module. Consult your local Mitsubishi representative.
Is the VX RDY LED off, and the MAIN ERR LED flashing?
A severe error has occurred, therefore take measures in accordance with the
error code.
If the same phenomenon remains after these measures, this may indicate a
hardware fault with the module. Consult your local Mitsubishi representative.
Is the VX RDY LED flashing?
Wait a moment because the VxWorks part is preparing.
If the VX RDY LED does not turn ON after waiting, and the WIN RDY LED
turns ON, product initialization or hardware self-diagnosis may have failed.
Use the Start menu in Windows perform a shutdown, and then turn the power
supply of this product OFF. After turning the power OFF, start the product in
offline mode, and then initialize the product.
Wait a moment because the VxWorks part is preparing.
If, after waiting, the VX RDY LED does not come on, then this may indicate a
hardware fault, therefore consult your local Mitsubishi representative.
Are all other LEDs off?
This may indicate a hardware fault with the product. Consult your local
Mitsubishi representative.
"bootapp.sys not found" is displayed on the display.
Содержание MELIPC MI5000 Series
Страница 1: ...MELIPC MI5000 Series User s Manual Application MI5122 VW ...
Страница 2: ......
Страница 18: ...16 MEMO ...
Страница 22: ...20 1 DIAGNOSTIC AND MAINTENANCE FUNCTIONS 1 1 Watchdog Timer WDT Function MEMO ...
Страница 42: ...40 5 iQSS FUNCTION MEMO ...
Страница 146: ...144 11 SECURITY FUNCTION 11 3 IP Filter Function MEMO ...
Страница 148: ...146 12 MELSOFT PRODUCT AND GOT CONNECTION FUNCTION 12 1 Connection Method MEMO ...
Страница 150: ...148 13 SYSTEM COUNT FUNCTION MEMO ...
Страница 152: ...150 14 TIMER EVENT FUNCTION MEMO ...
Страница 160: ...158 15 OS LINKING FUNCTIONS 15 3 Inter OS Event Notification Function MEMO ...
Страница 162: ...160 16 SERIAL INTERFACE SWITCHING FUNCTION MEMO ...
Страница 165: ...17 BASIC PARAMETERS 17 1 Basic Parameter List 163 17 Operation related setting Window ...
Страница 170: ...168 17 BASIC PARAMETERS 17 1 Basic Parameter List RAS setting Window ...
Страница 174: ...172 17 BASIC PARAMETERS 17 1 Basic Parameter List External device connection settings Window ...
Страница 177: ...17 BASIC PARAMETERS 17 1 Basic Parameter List 175 17 External device connection applicable settings Window ...
Страница 313: ...APPX Appendix 10 List of VxWorks Components 311 A MEMO ...
Страница 315: ...I 313 MEMO ...
Страница 319: ......