4. Using Test Mode
60
4.3. Test Menu 3:
Zero Span Adjustment for Analog Output
The following operations are available in the test mode.
When the ME-4210-SS96 optional plug-in module is not installed, this test menu will be skipped.
<To continue other test mode>
⇒
Select other test menu number and then press
.
<To close test mode>
⇒
Select "End" as the test menu number and then press .
You will return to the operation mode.
Test menu
SET
SET
Execute span adjustment for analog output CH2 to CH4.
The adjustment method is the same as
②
Analog Output CH1 Span Adjustment .
④
Analog output CH2 to
CH4 span adjustment
Execute zero adjustment for analog output CH2 to CH4.
The adjustment method is the same as
①
Analog Output CH1 Zero Adjustment .
③
Analog output CH2 to
CH4 zero adjustment
Execute span adjustment for analog output CH1.
Possible setting range : -50 to ±0 to +50
Adjustment is possible up to about ±0.3mA
■
Span adjustment movement
②
Analog output CH1
span adjustment
Note: For span adjustment,
measurement input is necessary.
mA
4
20
Input
0
<Single deflection>
Span
adjustment
value
mA
4
12
20
Input
0
<Double deflection>
Span
adjustment
value
Execute zero adjustment for analog output CH1.
Possible setting range : -50 to ±0 to +50
Adjustment is possible up to about ±0.3mA
■
Zero adjustment movement
①
Analog output CH1
zero adjustment
Note: For zero adjustment, set the
measurement input to zero.
mA
4
20
Input
0
Zero adjustment valu
e
Set the test menu number to "3".
Test menu
SET
SET
DISPLAY
SET
DISPLAY
SET
DISPLAY
SET
DISPLAY
Содержание ME96SSRA-MB
Страница 88: ...87 Installation 1 Dimensions ME96SSRA MB Optional Plug in Module ME 4210 SS96 ME 0040C SS96 ME 0052 SS96 ...
Страница 89: ...88 Installation 1 Dimensions Optional Plug in Module ME 0000MT SS96 Optional Plug in Module ME 0000BU SS96 ...
Страница 98: ...97 Installation 4 Wiring Diagram Optional Plug in Module ME 0000MT SS96 Optional Plug in Module ME 0000BU SS96 ...