3. Setting
45
3.11. Setting Menu 7:
Setting Periodic Active Energy, Rolling Demand, and Digital
Input/Output
SET
DISPLAY
SET
Set “on or off” of the digital input/output display.
When without the optional plug-in module, with ME-0000MT-SS96 or
ME-0000BU-SS96, this display will be skipped.
oFF
on
(
Not displayed
)
(
Displayed
)
⑤
Digital
input/output display
Set the method to reset the digital input.
When without the optional plug-in module, with ME-0000MT-SS96 or
ME-0000BU-SS96, this display will be skipped.
Reset method
(Setting value)
Description
(For details, refer to page 75.)
Auto
(Auto)
When the digital input is turned to OFF
(opened), the digital input state is
automatically turned to OFF (opened).
Latch
(HoLd)
When the digital input detects ON (closed)
once, even if the digital input is turned to OFF
(opened), the digital input state is retained as
ON (closed) until the operation of releasing the
latch is performed.
Note
When the ME-4210-SS96 optional plug-in module is installed, the “d.in1”
set
②
Control setting for switching time segments of periodic active energy
or
④
Rolling demand time setting, this display will be skipped.
⑥
Digital input reset
method
According to the setting flow (page 16 to 21), save the changed
contents, or continue to the other setting menu.
Setting Menu
Содержание ME96SSRA-MB
Страница 88: ...87 Installation 1 Dimensions ME96SSRA MB Optional Plug in Module ME 4210 SS96 ME 0040C SS96 ME 0052 SS96 ...
Страница 89: ...88 Installation 1 Dimensions Optional Plug in Module ME 0000MT SS96 Optional Plug in Module ME 0000BU SS96 ...
Страница 98: ...97 Installation 4 Wiring Diagram Optional Plug in Module ME 0000MT SS96 Optional Plug in Module ME 0000BU SS96 ...