3. Setting
44
3.11.
Setting Menu 7:
Setting Periodic Active Energy, Rolling Demand, and Digital
Input/Output
Set the periodic active energy, rolling demand, and digital input/output.
In the operation mode, press
and
simultaneously for 2 seconds or more, and the following operation becomes
available.
For more details about each function, refer to the corresponding pages.
Periodic Active Energy
⇒
page 72, Rolling Demand
⇒
page 73, digital input/ output
⇒
Set the setting menu number to “7”.
(as shown in the right figure)
Setting menu
SET
RESET
Set “on or off” of the periodic active energy display that enables
display of the electric energy divided into two time segments.
oFF
on
(
Not displayed
)
(
Displayed
)
①
Periodic Active
energy display
Set the control method to switch between time segments of
periodic active energy.
When without the optional plug-in module, with ME-0000MT-SS96 or
ME-0000BU-SS96, no item related to DI is displayed.
②
Control setting for
switching time
segments of periodic
active energy
<
Non:Not switched, COM.:Communication control,
d.in1:Digital input DI1, d.in2:Digital input DI2
>
non
COM.
d.in1
d.in2
Note1
.
When the ME-4210-SS96 optional plug-in module is installed, “d.in2” will be skipped.
The “d.in1” set
④
Rolling demand time setting, no item related to DI is displayed.
Note2
.
When the ME-0040C-SS96 and ME-0052-SS96 the optional plug-in module is installed,
this display will be skipped of
④
Rolling demand time setting set DI.
Set “on or off” of the rolling demand display.
oFF
on
(
Not displayed
)
(
Displayed
)
③
Rolling demand
display
Set the rolling demand time.
When without the optional plug-in module, with ME-0000MT-SS96 or
ME-0000BU-SS96, this display will be skipped.
④
Rolling demand
time setting
(
Manual
)
(
Digital input DI1
)
(
Digital input DI2
)
oFF
d.in1
d.in2
Note1
.
When the ME-4210-SS96 optional plug-in module is installed, “d.in2” will be skipped.
The “d.in1” set
②
Control setting for switching time segments of periodic active energy,
this display will be skipped.
Note2
.
When the ME-0040C-SS96 and ME-0052-SS96 the optional plug-in module is installed,
this display will be skipped of
②
Control setting for switching time segments of periodic
active energy set DI.
SET
DISPLAY
SET
DISPLAY
SET
DISPLAY
SET
DISPLAY
SET
DISPLAY