104
Specifications
7. Setting Table (Factory Settings and Customer Setting Note)
Setting menu No.
Setting items
Initial content
Memo
1
1.1
Phase wire system
3P4(3-phase 4-wire)
1.2
Display pattern
P04
1.2.1
Pattern P00
―
1.3
VT/direct selection
no(No VT)
1.3.1
Direct voltage
220/380V
1.3.2
VT secondary voltage
―
1.3.3
VT primary voltage
―
1.4
CT secondary current
5A
1.4.1
CT primary current
5A
1.5
Frequency
50Hz
1.6
Time constant for rolling demand (Interval time constant)
15min
1.6.1
Subinterval time constant
1min
1.7
Time constant for current demand
0s
2
2.1
Communication setting selection
CC or Mb.tCP
2.2
MODBUS
®
RTU address
1
2.2.1
MODBUS
®
RTU baud rate
19.2kbps
2.2.2
MODBUS
®
RTU parity
EVEn(even)
2.2.3
MODBUS
®
RTU stop bit
1
2.3
CC-Link station number
1
2.3.1
CC-Link baud rate
156kbps
2.3.2
CC-Link version
1.10
2.3.3
Communication reset
oFF
2.4
MODBUS
®
TCP IP address
192.168.3.10
MODBUS
®
TCP Subnet mask
255.255.255.0
MODBUS
®
TCP Default gateway existence
oFF(No existence)
MODBUS
®
TCP Default gateway
127.0.0.1
Communication reset
oFF
3
3.1
Current maximum scale
5A(CT primary
current)
3.1.1
Special current maximum scale
―
3.2
Voltage maximum scale
300V(±0 STEP)
3.3
Power maximum scale
4000W(±0 STEP)
3.3.1
Single / Double deflection
Single deflection
3.4
Reactive power maximum scale
4000var(±0 STEP)
3.5
Power factor scale
0.5(-0.5 to 1 to 0.5)
3.6
Expanded counting
Combination I
3.7
Harmonics display
oFF
4
4.1
Model name + option code
(Model name)
4.2
Version display
(Version)
4.3
Back light brightness
3
4.4
Back light auto off
Auto(Auto off)
4.5
Display update time
0.5s
5
5.1
Alarm item 1
non
5.1.1
Alarm value 1
―
5.2
Alarm item 2
non
5.2.1
Alarm value 2
―
5.3
Alarm item 3
non
5.3.1
Alarm value 3
―
5.4
Alarm item 4
non
5.4.1
Alarm value 4
―
5.5
Alarm delay time
―
5.6
Alarm cancel method
―
5.7
Back light flickers during alarms
―
5.8
Motor start-up current masking
oFF
5.8.1
Motor start-up current threshold
―
5.8.2
Motor start-up current delay time
―
5.9
Pulse / Alarm output 1 (With ME-4210-SS96)
PULSE(Pulse output)
5.9.1
Pulse output 1: output item
Wh
5.9.2
Pulse output 1: pulse unit
0.001kWh/pulse
5.10
Pulse / Alarm output 2 (With ME-4210-SS96)
AL (Alarm output)
5.10.1
Pulse output 2: output item
―
5.10.2
Pulse output 2: pulse unit
―
5.11
Pulse width
0.125s