When you set active power and reactive power as alarm element, the setting range is determined by the
standard value calculated using the following calculation formula.
■
The standard value of active power/reactive power
Measuring element
Calculation method for standard value
Active power
VT ratio × CT ratio × Intrinsic power (100%) kW
Reactive power
Note1: When you set to
‘Without VT (Voltage direct input)’, the VT ratio is 1. For intrinsic power, refer to the following table.
Note2: The calculated value is round to the nearest number as the table in the next page.
■
Intrinsic power
Phase wire
system
CT secondary
current
Rated voltage
Intrinsic power value
(100%
)
1-phase
2-wire
5 A
Direct input
(Line voltage)
110 V
0.5 kW
220 V
1.0 kW
440 V
2.0 kW
With VT
(Line voltage)
100 V, 110 V
0.5 kW
220 V
1.0 kW
1 A
Direct input
(Line voltage)
110 V
0.1 kW
220 V
0.2 kW
440 V
0.4 kW
With VT
(Line voltage)
100 V, 110 V
0.1 kW
220 V
0.2 kW
1-phase
3-wire
5 A
Without VT
(Line voltage)
220 V
1.0 kW
440 V
2.0 kW
1 A
220 V
0.2 kW
440 V
0.4 kW
3-phase
3-wire
5 A
Direct input
(Line voltage)
110 V
1.0 kW
220 V
2.0 kW
440 V
4.0 kW
With VT
(Line voltage)
100 V, 110 V
1.0 kW
220 V
2.0 kW
1 A
Direct input
(Line voltage)
110 V
0.2 kW
220 V
0.4 kW
440 V
0.8 kW
With VT
(Line voltage)
100 V, 110 V
0.2 kW
220 V
0.4 kW
3-phase
4-wire
5 A
Direct input
63.5/110 V
1.0 kW
100/173 V
110/190 V
2.0 kW
220/380 V
230/400 V
240/415 V
254/440 V
4.0 kW
277/480 V
5.0 kW
With VT
(Phase voltage)
63.5 V
1.0 kW
100 V, 110 V,
115 V, 120 V
2.0 kW
1 A
Direct input
63.5/110 V
0.2 kW
100/173 V
110/190 V
0.4 kW
220/380 V
240/415 V
254/440 V
0.8 kW
277/480 V
1.0 kW
With VT
(Phase voltage)
63.5 V
0.2 kW
100 V, 110 V,
115 V, 120 V
0.4 kW
Note: For reactive power and apparent power, read
‘kW’ in the above table as ‘kvar’ and ‘kVA’ respectively.