3. How to Set up
Example for Easy Setup
The following example illustrates an easy setup.
■
Setting Example
・
Model:
ME96SSEB-MB
・
Phase wire system:
3-phase 4-wire
・
Measuring element:
A, V, W, PF
・
Input Voltage:
220/380 V
・
CT primary current:
200 A
・
CT Secondary current: 5 A
・
MODBUS
RTU:
A
ddress:
1, B
aud rates:
19.2kbps, P
arity:
even, S
top bit:
1
■
Setting Procedure
shows the item where setting change is necessary.
Operating mode
Set the setting menu number to "1" and then press SET.
Setting Menu
The factory default is set to
“3P4 (3-phase 4-wire).” Just press SET.
Phase wire system
The factory default is set to
“P01.” Just press SET.
Display pattern
The factory default is set to "no (Without VT)
.” Just press SET.
VT/Direct voltag
e
The factory default is set to "220/380
V.” Just press SET.
Direct voltage
The factory default is set to "5 A." Just press SET.
CT secondary
current
Set to "200 A" and then press SET.
CTprimary
current
The factory default
is set to "0 s.” Just press SET
.
Current demand
time period
Set the setting menu number to "2" and then press SET.
Setting Menu
SET
Note: For details on the settings, refer to
SET
SET
SET
SET
SET
SET
SET
SET
Press
and
simultaneously for 2 seconds
RESET
SET