background image

P.B.

L.B.

TB1

PE

L
N

Breaker 3A

Unit Body

Unit Body

CN31

3

1

3

AC250V
2A F

ZNR2

F

1

T2

CN33

DSA1

ZNR1

Unit Body

7

3

1

5

CN71

SWL
(Service
 Switch)

(Service

LEDL

    LED)

1

3

4

3

2

1

5
6

CN45

T1

CN65

2

1

CN21

3

1

CN32

1
2
3
4

CNL12

CN605

5

4

3

2

1

LED402
(5VM)

LED502
(3150RST)

6

4

3

2

1

M-NET
Power Supply

CN40

(WDT)

LED009

LED201

CN41

(18007RST)

         SW71
(Termination Switch)

12

ON

OFF

3

1 2

TO M-NET  transmission line
(Centralized control line)

CNS3

A B

TB2

1

3

CN405

CN702

1

2

Unit Body

L

ON

W

ORKS

® 

transmission line

TB21

S

1 2

4

SW4

10

1

OFF

ON

OFF

ON

SW2

SW1

1

6

SW3

6

1

ON

OFF

0

1

5

2

3

4

6

7

8

9

0

1

5

2

3

4

6

7

8

9

SWU1

(1st digit)

SWU2

(2nd digit)

LED001

LED002

LED003

LED004

(Wink)

Power supply

220-240V~/N 50/60Hz

9

3-4 Electrical Wiring

Explanation of function switch

SW1-1

ON

OFF

Function switch
of local prohibit

local prohibit effective

local prohibit invalidity

ON

OFF

LOSSNAY is operation
from

 

L

ON

W

ORKS

®

 

LOSSNAY interlocks
with the indoor unit

Switch name

Function

OFF

Factory

setting

Operation local prohibit nv inputfrom
L

ON

W

ORKS

®

 becomes Effective when switch ON.

Operation local prohibit nv input from
L

ON

W

ORKS

®

 becomes invalid when switch OFF.

Note

Before turning
on the power supply

SW1-5 Function switch

of LOSSNAY

OFF

Please turn on the switch when LOSSNAY
is operation from L

ON

W

ORKS

®

.

Please turn off the switch when LOSSNAY
interlocks with the indoor units.

Before turning
on the power supply

ON

OFF

Mr.SLIM is operation
from

 

L

ON

W

ORKS

®

 

Mr.SLIM is not operation
from

 

L

ON

W

ORKS

®

 

SW1-6 Function switch

of Mr.SLIM

OFF

Before turning
on the power supply

ON

OFF

ON(test run) is transmitted
to the indoor units
OFF is transmitted to the
indoor units

SW1-9 Indoor units

test run switch

OFF

Always

ON

OFF

Connected cancellation
command is transmitted
to the indoor units
None

SW3-2 Initialization

switch of the air
conditioners units

OFF

Always

SW1-3

ON

OFF

Indoor temperature
state interval switch

Transmission interval
 (1minutes or more)

Transmission interval
 (10 minutes or more)

OFF

Before turning
on the power supply

SW1-2

ON

OFF

Used together
with MELANS switch

used together with MELNAS
not used together with MELNAS

OFF

Before turning
on the power supply

Set timing

SW

 *number of indoor unit should
  be connected 30 or less

Please turn on the switch when Mr.SLIM
is operation from L

ON

W

ORKS

®

.

Transformer

Switch

Function selection

M-NET address switch

Tremination selection switch
 (L

ON

W

ORKS

®

 )

SYMBOL EXPLANATION

Power circuit board

P.B

L.B

LM-AP main board

F

SWU1, 2

Service switch (L

ON

W

ORKS

®

 )

SWL

Fuse AC250V 2A F

NAME

SYMBOL

SW1, 2, 3

T1.2

SW71

L

ON

W

ORKS

®

 transmission line

Earth terminal

M-NET transmission line

Power source

LED

TB21

Power Supply switch connector

CN40/CN41

TB2

TB1

Maintenance LED
Use LED001 as Wink
 (L

ON

W

ORKS

®

 ) at SW2-1 ˜ 6 OFF

LED001 ˜ 004

Status LED

LED009/201/502/402

Service LED (L

ON

W

ORKS

®

 )

LEDL

NAME

SYMBOL

Terminal
block

Содержание LMAP02

Страница 1: ...ogether with MELANS 11 4 3 Initialization Settings of LONWORKS Network 12 5 Confirming Operation 13 5 1 Pre operation preparations and settings 13 5 2 Test operation procedure 13 6 Troubleshooting 14 6 1 Abstract 14 6 2 Troubleshooting 15 6 3 Error Code list 15 Before using the unit please read this Installation Manual carefully to ensure correct operation Store this Installation Manual in a locat...

Страница 2: ...ion may result in an electric shock fire or incorrect operation All electrical work must be performed by a licenced technician according to local regulations and the instructions given in this manual Any lack of electric circuit or any deficiency caused by installation may result in an electric shock or fire Wire and connect using the desired cables securely so that any external force from the cab...

Страница 3: ...lace at a temperature of more then 43 C or less than 15 C It may become the cause of modification and failure Safety dispose of the packing materials Tear apart and throw away plastic packaging bags so that children will not play with them If children play with a plastic bag which was not torn apart they face the risk of suffocation Be sure to shut off the power source of the unit and all the othe...

Страница 4: ...s bonded on the board please contact your dealer 7 5 R ø10 4 5 9 6 59 6 Detail of A 340 325 60 240 360 A TB1 Power supply terminal 200 240V 2 ø4 5 hole TB2 M NET transmission terminal TB21 LONWORKS transmission terminal 10 Item Power Source Current Consumption Dimensions Net Weight Operation Environment Installation Environment Description 220 240V 50 60 Hz 50 mA Maximum 340 H x 360 W x 59 6 D mm ...

Страница 5: ...User s Guide by Echelon Corporation Item Description Connected Equipment Number of Units LM AP can control 50 indoor units including LOSSNAY Item Description TMPN3150 10MHz Neuron CHIP FTT 10A Free Topology 78kbps Network Transceiver Performance 2 5 inputs second Average communication capacity 50 inputs second for one second Peak communication capacity MITSUBISHI ELECTRIC Multiple split type air c...

Страница 6: ...0n nvoSpaceTemp_n nv12n nvoAlarm_n nv16n nvoProOnOff_n nv20n nviProMode_n nv22n nviProSetPoint_n nv24n Alarm state Temperature state of indoor Thermo On Off state FanSpeed state Setpoint state both cool and heat Mode state On Off run state note1 The case of CITY MULTI is indicated note2 There is a case which cannot be used with the system configuration of the air conditioners units note3 n of the ...

Страница 7: ...re ø1 2mm to ø1 6mm Twist type 1 25mm2 to 2mm2 Use the wire which is recommended by Echelon Corporation For details refer to FTT 10A Free Topology Transceiver User s Guide For reference Cable Types and Txpical Parameters LONWORKS Network transmission wire Cable type Switch Capacity Fuse 3A 3A Breaker for wiring Breaker for Current Leakage 3A 3A 30mA 0 1 sec or less Wire dia AWG Rloop Ω km C nF km ...

Страница 8: ... Use M4 screws as shown in Fig below to fix the product To prevent the product from dropping make sure to fix four places CAUTION This unit does not have a water resistant design Always install the unit indoors or inside a control panel Install in an area capable of withstanding a 3 3 kg load 20 20 20 20 Installation space ...

Страница 9: ...31 CN33 CNS3 CN605 CNL12 CN702 TB21 2 Connect LONWORKS signal wire to 1 2 or 3 4 of signal wire terminal block TB21 TB21 1 and 3 as well as 2 and 4 of TB21 are connected inside the circuit board Connect the power supply wires and ground wire to L N and ground of terminal block TB1 Connect M NET signal wire to A and B of terminal block TB2 Connect the M NET transmission wire to transmission termina...

Страница 10: ...en LOSSNAY interlocks with the indoor units Before turning on the power supply ON OFF Mr SLIM is operation from LONWORKS Mr SLIM is not operation from LONWORKS SW1 6 Function switch of Mr SLIM OFF Before turning on the power supply ON OFF ON test run is transmitted to the indoor units OFF is transmitted to the indoor units SW1 9 Indoor units test run switch OFF Always ON OFF Connected cancellation...

Страница 11: ...r conditioner Independent LOSSNAY Or when operation is to be controlled from LONWORKS BMS etc connectedto the LOSSNAY remote control LOSSNAY selection switch SW1 5 ON 2 When sequencing LOSSNAY to the air conditioner sequenced LOSSNAY and not controlling operation from an LONWORKS BMS etc LOSSNAY selection switch SW1 5 OFF When sequencing LOSSNAY to the air conditioner the indoor unit and LOSSNAY s...

Страница 12: ...for details on the M NET wiring length Note 4 Set the M NET address so that it is not duplicated with other units ON OFF 1 2 3 4 5 6 7 8 9 10 ON OFF 1 2 3 4 5 6 7 8 9 10 ON OFF 1 2 3 4 5 6 7 8 9 10 Factory setting 247 CN41 OFF OFF CN41 M NET address of LM AP LM AP power switch connector Combined switch for LM AP MALANS OC central control SC on off switch OC power supply connector SWU2 1 201 to 250...

Страница 13: ...X2X0 8 900 TIA Category 5 900 Maximum node to node distance Belden 85102 500 Belden 8471 400 Level IV 22AWG 400 Units meters JY St Y 2X2X0 8 320 TIA Category 5 250 Maximum total wire length 500 500 500 500 450 The free topology transmission specification includes two components which must both be met for proper system operation The distance from each transceiver to all other transceiver and to the...

Страница 14: ...D003 and LED004 5 2 Test operation procedure 1 Test operation of the indoor unit from LM AP 1 Turn on SW1 9 of LM AP If there is even one indoor unit that is not running the LM AP may not correctly recognize the indoor unit Refer to the next chapter Troubleshooting 2 Finally turn OFF SW1 9 and verify that all indoor units are stopped 2 Test operation of the indoor unit from LONWORKS If there is an...

Страница 15: ...2 is all off the indoor unit may be troubled Check the connection and setting of all indoor units CN40 41 If the power supply unit is connected insert the jumper connector to CN41 If the power supply unit is not connected insert the jumper connector to CN40 SW71 LONWORKS The switch sets the termination of LONWORKS network According to the system design of LONWORKS network check whether it is prope...

Страница 16: ...wer supply Even if the operation is tested on LM AP the LOSSNAY does not operate 1 The LM AP is not completely initialized 2 Setting on M NET side is not properly completed 3 If MELANS is used in combination LM AP is not registered to MELANS 4 LONWORKS network transmission line is not properly connected 5 The termination of LONWORKS network is not properly set 6 Binding of LONWORKS network is not ...

Страница 17: ...fer to 2 4 Refer to 4 4 Refer to 4 5 Refer to 4 6 Error content Cause Checking method and remedy Independent combi ned LOSSNAY can not be operated from the LON side 1 The LM AP is not completely initialized 2 Setting on M NET side is not properly completed 3 If MELANS is used together LM AP is not registered to MELANS 4 LONWORKS network transmission wire is not properly connected 5 The termination...

Страница 18: ...transmission wire If recipient of transmission is LM AP Defect in transmission line TB2 between LM AP Interrupted power LM AP power supply TB1 Blown fuse F1 in LM AP disconnection on the loose connector CN605 CN65 CN32 CN33 CN31 Damage transformer in LM AP T1 T2 Damage circuit board L B P B Check that there are no duplicate addresses After correcting problem reset power supply Check for defects On...