• Select and operate Pre-heat unit that Lossnay supply
intake air temperature becomes between –10˚C to
40˚C.
• Pre-heat unit must be controlled to stop during
Lossnay not operating.
●
Select a position for introducing the outside air where
no exhaust or combustion gases will be sucked into
the product and where it will not be covered by snow.
(Failure to ensure a supply of fresh air can result in pro-
ducing a state of oxygen deficiency inside the room.)
●
Select an adequately sturdy position for installing the
product and install it properly and securely. (Injury may
result if the product should fall.)
●
Use the designated electrical wires for the terminal board
connections, and connect the wires securely so that
they will not become disconnected.
(Failure to ensure proper connections may result in fire.)
●
When passing metal ducts through wooden buildings
clad with metal laths, wire laths or metal, these ducts
must be installed in such a way that they will not make
electrical contact with the metal laths, wire laths or metal
sheets. (Power leakage can cause ignition.)
●
The outside ducts must be tilted at a gradient (1/30 or
more) down toward the outdoor area from Lossnay unit,
and properly insulated.
(The entry of rain water may cause power leaks, fire or
damage to household property.)
●
Gloves should be worn when doing the installation work.
(Failure to heed this warning may result in injury.)
●
A dedicated circuit breaker must be installed at the ori-
gin of mains power supply. This circuit breaker must be
provided with a means for locking (lock and key).
●
Connect the product properly to ground.
(Malfunctioning or power leaks can cause electrical
shock.)
●
An isolator switch having a minimum contact gap of 3
mm in all poles must be provided as a means of dis-
connecting the power supply.
LGH-50RX
3
-CAN
LGH-100RX
3
-CAN
LGH-200RX
3
-CAN
Lossnay
Models:
Instruction manual for using and for installing the product.
(Instruction manual for the user, the dealer, and for the person qualified for the installation work.)
Since this model LGH-50, 100, 200RX3-CAN is designed only for Canada, the sections “Safety precautions”,
“Electric installation” and “Specifications” are partially different from the same sections included in the manual for
LGH-50, 100, 200RX3-E series
Please be sure to read carefully the supplied instruction manual before using and before installing the product.
No
disassembly
WARNING
●
This product must not be disassembled under any cir-
cumstances. Only authorized repair technicians are
qualified to conduct disassembly and repairs.
(Failure to heed this warning may result in fire, electrical
shock or injury.)
●
Do not install this product in a refrigerated warehouse,
heated swimming pool or other location where the tem-
perature and humidity are significantly different.
(Failure to heed this warning may result in electrical
shock or malfunctioning.)
●
Do not install this product where it will be directly ex-
posed to the rain.
(Failure to heed this warning may result in electrical
shock or malfunctioning.)
●
Do not install this product in a location where acid, alkali
or organic solvent vapors, paints or other toxic gases,
gases containing corrosive components or high con-
centrations of oily smoke are present.
(Failure to heed this warning may result not only in mal-
functioning but also fire, power leakage and electrical
shock.)
●
Do not use this product outside the range of its rated
voltage and control capacity.
Single phase, 208-230V 60Hz
(Failure to heed this warning may result in fire or electri-
cal shock.)
●
Install this product in an environment where the tem-
perature ranges from –10°C to +40°C and the relative
humidity is less than 80%. If condensation is expected
to form, heat up the fresh outside air using a duct heater,
etc.
●
Install this product in an environment where the outside
air intake meets the following conditions: temperature
range is between –10°C and +40°C and the relative
humidity is 80% or less.
●
Using Pre-Heat Unit
• Make sure to install Pre-heat unit where outdoor air
temperature is below –10˚C, or condensation is
expected to form.
• Pre-heat unit must be installed from Lossnay unit as
far as possible, because of fire prevention.
Safety precautions
Prohibited
Connect the
grounding wire.
Instructions
must be
followed