4.15
HEAT PUMP INHIBITIONS
The following inhibitions are set for the protection of the heat pump:
-
operation outside envelope
-
based on the external air temperature
The individual functions are described below.
4.15.1
OPERATION OUTSIDE ENVELOPE
See the paragraph dedicated to the Power+ driver.
4.15.2
EXTERNAL AIR TEMPERATURE
The purpose of this function is to protect the machine, preventing the operation of the compressor in heating or cooling mode when the external air
temperature exceeds the rated operating limits of the unit, set through the parameter, based on the functions described below:
Low external temperature inhibition
Attivo
OFF
Unit block
External air T (B4) [°C]
External low T unit stop
setpoint
(133Z)
External low T unit stop
hysteresis (0312)
High external temperature inhibition
Attivo
OFF
Unit block
External air T (B4) [°C]
External high T unit
stop setpoint
(0515)
External high T unit stop
hysteresis (0516)
Any heating request is met with the available resources (delivery heaters, alternative heat source).
Limits in HEAT only operating mode:
133Z
and
0515
and related hysteresis
Limits in DHW only operating mode:
133Z
and
0515
and related hysteresis
Limits in COLD only operating mode:
133Q
and
0526
and related hysteresis
Limits in DHW + COLD operating mode:
133Z
and
0515
during DHW operation and
133Q
and
0526
during COLD operation.
Limits in DHW + HOT operating mode:
133Z
and
0515
both during DHW and HOT operation.
For the default values of the various parameters, see the parameters table.