TM_i-BX(-N)_NC05_00_06_20_EN
MEHITS S.p.A.
●
TECHNICAL MANUAL
Version NC05 - Translation of the Original Instructions
18
Num Par
Description
Default
Unit
Min.
Max.
P019D
Configuration of digital input 9 (0: LOW ENERGY FARE; 1: BACKUP BOILER)
0
-
0
1
P019E
Logic of summer/winter output (0: NORMALLY OPEN; 1: NORMALLY CLOSED)
0
-
0
1
P019F
Configuration NO4 pCOe n.1 (0: ZONE HT1; 1: SUMMER/WINTER)
0
-
0
1
2.4.3
MENÙ 02
Num Par
Description
Default
Unit
Min.
Max.
P0200
Type of recirculation DHW (0: by DIN; 1: scheduler DHW)
0
-
0
1
P0201
Time DHW recirculation
5
min
0
99
P0202
Type of configuration DHW (0: Disabled; 1: Heat pump only; 2: Heaters only; 3: Heat pump +
Heaters)
0
-
0
3
P0205
Enable modulating of the DHW pump (0:NO; 1:YES)
0
-
0
1
P0206
Setpoint pump DHW
30.0
°C
-999.9
999.9
P0207
Differential pump DHW
10.0
°C
0.0
99.9
P0208
Enable overboost for DHW (0:NO; 1:YES)
1
-
0
1
P0209
Set overboost DHW
60.0
°C
0.0
999.9
P0210
Differential Overboost
5.0
°C
0.0
99.9
P0211
Antilegionella temperature setpoint
65.0
°C
-99.9
99.9
P0212
Fixed days or period for antilegionella (0: Enabled fixed days; 1: Enabled period)
0
-
0
1
P0213
Enable the antilegionella cycle on Monday (0:NO; 1:YES)
1
-
0
1
P0214
Enable the antilegionella cycle on Tuesday (0:NO; 1:YES)
0
-
0
1
P0215
Enable the antilegionella cycle on Wednesday (0:NO; 1:YES)
0
-
0
1
P0216
Enable the antilegionella cycle on Thursday (0:NO; 1:YES)
0
-
0
1
P0217
Period for antilegionella cycle
1
d
1
30
P0218
Enable the antilegionella cycle on Friday (0:NO; 1:YES)
0
-
0
1
P0219
Enable the antilegionella cycle on Saturday (0:NO; 1:YES)
0
-
0
1
P0220
Enable the antilegionella cycle on Sunday (0:NO; 1:YES)
0
-
0
1
P0221
Hour start antilegionella cycle
2
h
0
23
P0222
Enable antilegionella (0:NO; 1:YES)
0
-
0
1
P0223
Antilegionella type (0: ONLY HEAT PUMP; 1: ONLY HEATERS; 2: HEAT PUMP)
0
-
0
2
P0224
Threshold for alarm no antilegionella
2
d
0
23
P0225
Maximum time for antilegionella cycle
180
min
1
500
P0226
Min time unit work for plant
20
min
0
500
P0227
Max time unit work for DHW
60
min
0
500
P0228
Enable antifreeze DHW (0:NO; 1:YES)
1
-
0
1
P0229
Setpoint antifreeze DHW
5.0
°C
0
999.9
P0230
Differential antifreeze DHW
3.0
°C
0
999.9
P0231
Time of change status of 3way valve
12
0
99.9
P0232
Enable Analogic input B3 (0:NO; 1:YES)
0
-
0
1
P0233
Enable DHW sniffer (0:NO; 1:YES)
0
-
0
1
P0234
Substitution temperature with heaters
-20.0
°C
-20.0