8 - 36
8. ETHERNET CONNECTION
8.4 PLC Side Setting
[Network parameter] of GX Developer
(1) Network parameter
: Necessary : As necessary : Not necessary
*1
When using Q170MCPU, set the start I/O to 0070
H
.
*2
Specify the same network No. as that of the GOT.
*3
Do not set the same station No. as that of the GOT.
*4
Set when using Ethernet module in a redundant QnPRHCPU
system.
(2) Operation setting
: Necessary : As necessary : Not necessary
*1
Because port No. 5001 is fixed, these items operate at the
following setting without relations to the setting given here.
POINT
POINT
POINT
When changing the network parameter
After writing the network parameter to the PLC CPU,
operate the PLC CPU ether turning OFF and then ON
or resetting.
Item
Set value
Setting
necessity at
GOT
connection
Network type
Ethernet (fixed)
Starting I/O No.
*1
0000
H
Network No.
*2
1
Group No.
0 (fixed)
Station No.
*3
2
Mode
Online (fixed)
Operation setting
Refer to (2)
Initial settings
(Use default value)
Open settings
Router relay parameter
Station No.<->IP information
FTP Parameters
E-mail settings
Interrupt settings
Redundant settings
*4
Routing Parameters
Refer to (3)
Item
Set value
Setting
necessity at
GOT
connection
Communication data code
*1
(Use default value)
IP address
192.168.0.19
Initial timing
*1
(Use default value)
Send frame setting
Enable Write at RUN time
*1
TCP Existence confirmation
setting
• Communication
date code
: [Binary code]
• Initial timing
: "Always wait for OPEN"
(Communication is applicable while
stopping the PLC CPU.)
• Enable Write at
RUN time
: [Enable Write at RUN time] (Writing
Data is applicable while running the
PLC CPU.)
Содержание GT15
Страница 2: ......
Страница 34: ...A 32 ...
Страница 92: ......
Страница 110: ...2 18 2 DEVICE RANGE THAT CAN BE SET 2 9 MELSEC WS ...
Страница 134: ...3 24 3 ACCESS RANGE FOR MONITORING 3 7 Connection to the Head Module of CC Link IE Field Network System ...
Страница 186: ...5 10 5 BUS CONNECTION 5 2 System Configuration ...
Страница 218: ...5 42 5 BUS CONNECTION 5 4 Precautions ...
Страница 254: ...6 36 6 DIRECT CONNECTION TO CPU 6 6 Precautions ...
Страница 286: ...7 32 7 COMPUTER LINK CONNECTION 7 6 Precautions ...
Страница 350: ...8 64 8 ETHERNET CONNECTION 8 5 Precautions ...
Страница 368: ...9 18 9 MELSECNET H CONNECTION PLC TO PLC NETWORK 9 5 Precautions ...
Страница 420: ...11 26 11 CC Link IE CONTROLLER NETWORK CONNECTION 11 5 Precautions ...
Страница 440: ...12 20 12 CC Link IE FIELD NETWORK CONNECTION 12 5 Precautions ...
Страница 490: ...13 50 13 CC Link CONNECTION INTELLIGENT DEVICE STATION 13 5 Precautions ...
Страница 510: ......
Страница 564: ...15 54 15 INVERTER CONNECTION 15 7 Precautions ...
Страница 668: ......
Страница 712: ...21 12 21 MULTIPLE GT14 GT12 GT11 GT10 CONNECTION FUNCTION 21 5 Precautions ...
Страница 713: ...MULTI CHANNEL FUNCTION 22 MULTI CHANNEL FUNCTION 22 1 ...
Страница 714: ......
Страница 760: ...22 46 22 MULTI CHANNEL FUNCTION 22 5 Multi channel Function Check Sheet ...
Страница 761: ...FA TRANSPARENT FUNCTION 23 FA TRANSPARENT FUNCTION 23 1 ...
Страница 762: ......
Страница 860: ...REVISIONS 4 ...
Страница 863: ......