5.4 PLC Side Setting
5 - 63
5
E
T
H
E
RNET CONNEC
T
ION
(c)
Ethernet setting
*1
Set the same value as that of GOT N/W No.
*2
Set a value different from that of the GOT PLC No. and the PLC No. of other PLCs on the same network.
(3) Checking communication state of Connecting to Built-in Ethernet port CPU
(a)
When using the Command Prompt of Windows.
Execute a Ping command at the Command Prompt of Windows.
• When normal communication
C:\>Ping 192.168.3.1
Reply from 192.168.3.1: bytes=32 time
<10ms TTL=32
• When abnormal communication
C:\>Ping 192.168.3.1
Request timed out.
(b)
When abnormal communication
At abnormal communication, check the followings and execute the Ping command again.
• Cable connecting condition
• Confirmation of switch and network parameter setting
• Operation state of PLC CPU (faulty or not)
• The IP address of Built-in Ethernet port CPU specified in the ping command
POINT
POINT
POINT
Ethernet diagnostics of GX Works2
Ethernet diagnostics of GX Works2 is available to a Ping test from the PLC.
For details of Ethernet diagnostics of GX Works2, refer to the following manual.
➠
QCPU User's Manual (Hardware Design, Maintenance and Inspection)
➠
MELSEC-L CPU Module User's Manual (Hardware Design, Maintenance and
Inspection)
5.4.8
Connecting to Ethernet module (Q/L Series)
This section describes the settings of the GOT and Ethernet module (Q Series) in the following case of the system
configuration.
POINT
POINT
POINT
Ethernet module (Q/L Series)
For details of the Ethernet module (Q/L Series), refer to the following manual.
➠
Q Corresponding Ethernet Interface Module User's Manual (Basic)
➠
MELSEC-L Ethernet Interface Module User's Manual (Basic)
Item
Set value
Ethernet setting No.1
Host
*
-
N/W No.
1
*1
1
*1
PLC No.
2
*2
3
*2
Type
QnUD(P)V/QnUDEH
QnUD(P)V/QnUDEH
IP address
192.168.3.1
192.168.3.2
Port No.
5001
5001
Communication
UDP (fixed)
UDP (fixed)
Содержание GOT2000 Series
Страница 2: ......
Страница 84: ......
Страница 432: ...6 58 6 6 Precautions ...
Страница 578: ...9 54 9 6 Precautions ...
Страница 726: ...12 84 12 5 Precautions ...
Страница 756: ......
Страница 822: ...14 66 14 4 Device Range that Can Be Set ...
Страница 918: ...15 96 15 7 Precautions ...
Страница 930: ...16 12 16 6 Precautions ...
Страница 963: ...MULTIPLE GOT CONNECTIONS 19 GOT MULTI DROP CONNECTION 19 1 20 MULTIPLE GT21 CONNECTION FUNCTION 20 1 ...
Страница 964: ......
Страница 1002: ...19 38 19 7 Precautions ...
Страница 1022: ...20 20 20 5 Precautions ...
Страница 1023: ...MULTI CHANNEL FUNCTION 21 MULTI CHANNEL FUNCTION 21 1 ...
Страница 1024: ......
Страница 1047: ...21 3 GOT Side Settings 21 23 21 MULTI CHANNEL FUNCTION Example Setting example for Ethernet connection 4 channels ...
Страница 1054: ...21 30 21 5 Multi channel Function Check Sheet ...
Страница 1055: ...FA TRANSPARENT FUNCTION 22 FA TRANSPARENT FUNCTION 22 1 ...
Страница 1056: ......
Страница 1223: ......