7 WIRING
53
7
7
WIRING
This chapter describes the wiring to the GOT power supply section.
For the connection with a PLC, refer to the following.
GOT2000 Series Connection Manual For GT Works3 Version1
For the dimensional drawing of connection cables, refer to the following.
General preventive measures against noise
There are two kinds of noises: Radiated noise that is transmitted into the air and Conductive noise that is
directly transmitted along connected lines. Countermeasures must be taken considering both kinds of noises
and referring to the following 3 points.
• Protecting against noise
Keep signal lines away from noise sources such as a power cable or a high-power drive circuit.
Shield the signal lines.
• Reducing generated noise
Use a noise filter, etc. to reduce the level of the noise generated due to a source such as a high-power motor
drive circuit.
Attach surge killers to the terminals on the no fuse breakers (NFB), electromagnetic contactors, relays,
solenoid valves, and generators to suppress noise interference.
• Releasing noise to the ground
Make sure to connect the ground cable to the ground.
Use a short and thick cable to lower its ground resistance.
Ground the power system and the control system separately.
Be sure to shut off all phases of the external power supply used by the system before wiring.
Failure to do so may result in an electric shock, product damage or malfunctions.
Please make sure to ground FG terminal of the GOT power supply section by applying 100
Ω
or less which is used
exclusively for the GOT.
Not doing so may cause an electric shock or malfunction.
Correctly wire the GOT power supply section after confirming the rated voltage and terminal arrangement of the
product.
Not doing so can cause a fire or failure.
Exercise care to avoid foreign matter such as chips and wire offcuts entering the GOT.
Not doing so can cause a fire, failure or malfunction.
Tighten the terminal screws of the GOT power supply section in the specified torque range.
Undertightening can cause a short circuit or malfunction.
Overtightening can cause a short circuit or malfunction due to the damage of the screws or the GOT.
WARNING
WIRING PRECAUTIONS
•
•
•
•
•
Plug the communication cable into the connector to be connected, and tighten the mounting screws and the terminal
screws in the specified torque range.
Undertightening can cause a short circuit or malfunction.
Overtightening can cause a short circuit or malfunction due to the damage of the screws or unit.
CAUTION
WIRING PRECAUTIONS
•
Содержание GOT SIMPLE Series
Страница 1: ...GOT SIMPLE Series User s Manual GS21 model ...
Страница 2: ......
Страница 20: ...18 MEMO ...
Страница 24: ...22 1 OVERVIEW 1 1 Features MEMO ...
Страница 34: ...32 3 SPECIFICATIONS 3 4 GOT Connector Specifications MEMO ...
Страница 40: ...38 4 PART NAME 4 3 Bottom MEMO ...
Страница 62: ...60 7 WIRING 7 2 Wiring Inside and Outside the Panel MEMO ...
Страница 76: ...74 10 LANGUAGE SETTING LANGUAGE 10 1 Display language setting MEMO ...
Страница 130: ...128 12 DISPLAY AND OPERATION SETTINGS GOT SET UP 12 7 IP Filter Setting MEMO ...
Страница 160: ...158 14 CLOCK SETTINGS TIME SETTING AND DISPLAY 14 1 Time Setting and Display MEMO ...
Страница 268: ...266 16 GOT SELF CHECK DEBUG 16 3 FX3U ENET ADP Communication Setting Function MEMO ...
Страница 274: ...272 17 MAINTENANCE 17 3 Clean MEMO ...
Страница 280: ...278 20 ERROR MESSAGE LIST MEMO ...
Страница 296: ...294 22 TROUBLESHOOTING 22 1 GOT Restoration Sheets MEMO ...
Страница 298: ...296 23 CONNECTION MEMO ...
Страница 305: ...24 APPENDIX 24 1 External Dimensions 303 24 MEMO ...
Страница 309: ......