3. SPECIFICATIONS
3.1 General Specifications
3 - 1
1
OV
E
R
VI
EW
2
S
YSTE
M
CONF
IGURA
TION
3
SPEC
IFI
CA
TIO
NS
4
PA
R
T
S
N
A
M
E
5
UL, cUL
ST
ANDARDS AND
EMC DIRECTIVE
6
IN
ST
AL
L
A
TI
ON
7
WIRING
8
OP
TI
ON
3.
SPECIFICATIONS
3.1 General Specifications
*1
Do not use or store the GOT under pressures higher than the atmospheric pressure of altitude 0m (0ft.).
Failure to observe this instruction may cause a malfunction.
When the air inside the control panel is purged by pressurization, the surface sheet may be lifted by high pressure. As a result,
the touch panel may be difficult to press, and the sheet may be peeled off.
*2
This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical
power distribution network and the machinery within the premises.
Category II applies to equipment for which electrical power is supplied from fixed facilities.
The surge voltage withstand level for up to the rated voltage of 300V is 2500V.
*3
This index indicates the degree to which conductive pollution is generated in the environment where the equipment is used.
In pollution degree 2, only non-conductive pollution occurs but temporary conductivity may be produced due to condensation.
Item
Specifications
Operating ambient
temperature
Display section
0 to 50
Other than
display section
0 to 55 (when horizontally installed), 0 to 50 (when vertically installed)
Storage ambient temperature
-20 to 60
Operating ambient humidity
10 to 90%, non-condensing (WBT: 39 )
Storage ambient humidity
10 to 90%, non-condensing
Vibration resistance
Conforms to
JIS B 3502 and
IEC 61131-2
Frequency
Acceleration
Half-
amplitude
Sweep count
Under
intermittent
vibration
5 to 8.4Hz
-
3.5mm
10 times each in
X, Y and Z
directions
8.4 to 150Hz
9.8m/s
2
-
Under
continuous
vibration
5 to 8.4Hz
-
1.75mm
-
8.4 to 150Hz
4.9m/s
2
-
Shock resistance
Conforms to JIS B 3502, IEC 61131-2 (147 m/s
2
, 3 times each in X, Y and Z directions)
Operating atmosphere
Must be free of lamp black, corrosive gas, flammable gas, or excessive amount of electro
conductive dust particles and must be no direct sunlight. (Same as for saving)
Operating altitude
*1
2000 m (6562 ft) max.
Installation location
Inside control panel
Overvoltage category
*2
II or less
Pollution degree
*3
2 or less
Cooling method
Self-cooling
Grounding
Class D grounding (100 or less), to be connected to the panel when grounding is not possible.
Содержание Got 1000
Страница 1: ......
Страница 2: ......
Страница 14: ...A 12 ...
Страница 26: ...1 4 1 OVERVIEW 1 1 Features ...
Страница 34: ...2 8 2 SYSTEM CONFIGURATION 2 2 System Equipment ...
Страница 38: ...3 4 3 SPECIFICATIONS 3 3 Power Supply Specifications ...
Страница 42: ...4 4 4 PARTS NAME 4 3 Rear Face ...
Страница 54: ...6 6 6 INSTALLATION 6 5 Installation Procedure ...
Страница 104: ...10 18 10 COMMUNICATION INTERFACE SETTING COMMUNICATION SETTING 10 3 Ethernet Setting ...
Страница 134: ...12 4 12 CLOCK SETTINGS AND BATTERY STATUS DISPLAY TIME SETTING AND DISPLAY 12 1 Time Setting and Display ...
Страница 226: ...13 92 13 FILE DISPLAY AND COPY PROGRAM DATA CONTROL 13 2 Various Data Control ...
Страница 250: ...15 2 15 CLEANING DISPLAY SECTION CLEAN ...
Страница 264: ...16 14 16 INSTALLATION OF COREOS BOOTOS AND STANDARD MONITOR OS 16 5 CoreOS ...
Страница 272: ...17 8 17 MAINTENANCE AND INSPECTION 17 5 Backlight Shutoff Detection ...
Страница 298: ...App 6 APPENDICES Appendix 1 External Dimensions ...
Страница 302: ...App 10 APPENDICES Appendix 3 Transportation Precautions ...
Страница 306: ...REVISIONS 2 ...
Страница 309: ......
Страница 310: ......