11 - 10
11. CONNECTION TO CHINO CONTROLLER
11.3 Connection Diagram
11.3 Connection Diagram
The following diagram shows the connection between the
GOT and the PLC.
11.3.1 RS-232 cable
Connection diagram
RS232 connection diagram 1)
*1
Terminal number of the controller and the converter differ
depending on the model.Refer to the following table.
*1
For KP2000 series, the terminal No. differs according to the
model.
*2
This indicates the symbols of the position 10) (third zone) of
the following models.
Model: KP2 4) 5) 6) 7) 8) 9) 10) – 12) 13) 14)
For the symbol B, two terminal numbers are available. Select
as necessary.
Precautions when preparing a cable
(1) Cable length
The length of the RS-232 cable must be 15m or less.
(2) GOT side connector
For the GOT side connector, refer to the following.
1.4.1 GOT connector specifications
(3) CHINO controller side connector
Use the connector compatible with the CHINO
controller side module.
For details, refer to the user's manual of the CHINO
controller.
Signal
name
Controller
Converter
LT300
LT400
DZ1000,
DZ2000
DB1000
DB2000
SC8-10
Terminal
No.
Terminal
No.
Terminal
No.
Terminal
No.
Terminal
No.
Terminal
No.
SD
11
11
19
13
27
2
RD
13
13
21
12
26
1
SG
15
15
23
14
28
3
Signal
name
Controller
KP1000
KP2000
SE3000
AL3000
AH3000
Terminal
No.
Terminal No.
*1
Terminal
name
Terminal
name
R
*2
, B
*2
, C
*2
, D
*2
B
*2
, E
*2
SD
13
27
30
SD
SD
RD
12
26
29
RD
RD
SG
14
28
31
SG
SG
CHINO controller
side, Interface
converter
1
2
3
4
5
6
7
8
9
-
GOT side
CD
RD(RXD)
SD(TXD)
ER(DTR)
SG
DR(DSR)
RS(RTS)
CS(CTS)
-
FG
-
SD
RD
-
SG
Содержание GOT 1000 Series
Страница 2: ......
Страница 76: ...1 46 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring ...
Страница 78: ......
Страница 114: ...2 36 2 CONNECTION TO IAI ROBOT CONTROLLER 2 7 Precautions ...
Страница 232: ...5 18 5 CONNECTION TO OMRON TEMPERATURE CONTROLLER 5 7 Precautions ...
Страница 254: ...6 22 6 CONNECTION TO KEYENCE PLC 6 4 Device Range that Can Be Set ...
Страница 404: ...14 14 14 CONNECTION TO PANASONIC SERVO AMPLIFIER 14 7 Precautions ...
Страница 426: ...15 22 15 CONNECTION TO PANASONIC INDUSTRIAL DEVICES SUNX PLC 15 6 Device Range that Can Be Set ...
Страница 432: ...REVISIONS 3 ...
Страница 435: ......