4.3 Ethernet Connection
4.3.1
System configuration
*1
The destination connected with the twisted pair cable varies with the configuration of the applicable Ethernet network system.
Connect to the Ethernet module, hub, transceiver or other system equipment corresponding to the applicable Ethernet network
system.
*2
A length between a hub and a node.
The maximum distance differs depending on the Ethernet device to be used.
The following shows the number of the connectable nodes when a repeater hub is used.
• 10BASE-T: Max. 4 nodes for a cascade connection (500m)
• 100BASE-TX: Max. 2 nodes for a cascade connection (205m)
When switching hubs are used, the cascade connection between the switching hubs has no logical limit for the number of
cascades.
For the limit, contact the switching hub manufacturer.
*3
When connecting GT16 of the function version A to an equipment that meets the 10BASE (-T/2/5) standard, use the switching
hub and operate in a 10Mbps/100Mbps mixed environment.
For how to check the function version, refer to the following.
GT16 User's Manual (Hardware)
*4
Product manufactured by OMRON Corporation. For details of the product, contact OMRON Corporation.
*5
If it is connected to devices other than the GOT using the connection, the number of connectable GOTs decreases.
For details, refer to the OMRON PLC user's manual.
*6
There is no restriction for the number of GOTs. However, if the number of GOTs increases, the communication becomes high-
loaded, and it may affect the communication performance.
*7
GT14 models compatible with Ethernet connection are only GT1455-QTBDE, GT1450-QMBDE and GT1450-QLBDE.
Ethernet
module
CS1H, CS1G, CS1D,
CJ1H, CJ1M, CJ1G,
CJ2H
GOT
Connection cable
Ethernet (OMRON), Gateway
Communication driver
PLC
Connection cable
GOT
Number of connectable
equipment
Series
Ethernet
module
*4
Cable model
Maximum
segment
length
*2
Option device
Model
*3
CS1H
CS1G
CS1D
CS1W-
ETN21
CS1W-EIP21
Twisted pair cable
*1
• 10BASE-T
Shielded twisted pair cable (STP)
or unshielded twisted pair cable
(UTP):
Category 3, 4, and 5
• 100BASE-TX
Shielded twisted pair cable (STP):
Category 5 and 5e
100m
- (Built into GOT)
*7
When PLC:GOT is N:1
The following shows the
number of PLCs for 1 GOT
<For GT16, GT14>
TCP: 128 or less
UDP: 128 or less
<For GT15, GT12>
TCP: 10 or less
UDP: 128 or less
When PLC:GOT is 1:N
The following shows the
number of GOTs for 1 PLC
TCP: 16 or less
*5
UDP: No limit number
*6
GT15-J71E71-100
CS1D
CS1D-
ETN21D
100m
- (Built into GOT)
*7
GT15-J71E71-100
CJ1H
CJ1M
CJ1G
CJ1W-
ETN21
CS1W-EIP21
100m
- (Built into GOT)
*7
GT15-J71E71-100
CJ2H-
CPU6 -
EIP
CJ2M-
CPU3
-
100m
- (Built into GOT)
*7
GT15-J71E71-100
CJ1W-
ETN21
CS1W-EIP21
100m
- (Built into GOT)
*7
GT15-J71E71-100
CJ2H-
CPU6 -
CJ2M-
CPU1
CJ1W-
ETN21
CS1W-EIP21
100m
- (Built into GOT)
*7
GT15-J71E71-100
Содержание GOT 1000 Series
Страница 2: ......
Страница 76: ...1 46 1 PREPARATORY PROCEDURES FOR MONITORING 1 6 Checking for Normal Monitoring ...
Страница 78: ......
Страница 114: ...2 36 2 CONNECTION TO IAI ROBOT CONTROLLER 2 7 Precautions ...
Страница 232: ...5 18 5 CONNECTION TO OMRON TEMPERATURE CONTROLLER 5 7 Precautions ...
Страница 254: ...6 22 6 CONNECTION TO KEYENCE PLC 6 4 Device Range that Can Be Set ...
Страница 404: ...14 14 14 CONNECTION TO PANASONIC SERVO AMPLIFIER 14 7 Precautions ...
Страница 426: ...15 22 15 CONNECTION TO PANASONIC INDUSTRIAL DEVICES SUNX PLC 15 6 Device Range that Can Be Set ...
Страница 432: ...REVISIONS 3 ...
Страница 435: ......