8 CANopen
®
417 Mode
8.10 Control Word/Status Word
164
FX
3U
-CAN User's Manual
8.10.2 Status word
This Car drive Status word is equivalent to object H6041 in the CiA
®
402-2 V3.0 specification.
Bit No.
Item
Description / set range
Bit 0
rtso
Ready to switch on
Bit 1
so
Switched on
Bit 2
oe
Operation enabled
Bit 3
f
Fault
Bit 4
ve
Voltage enabled
ON when high voltage is applied to the Power drive system.
Bit 5
qs
Quick stop
OFF When the Power drive system is reacting on a quick stop request.
Bit 6
sod
Switch on disabled
Bit 7
w
Warning
ON when being a warning condition. The status of the Power drive system Finite state automaton will not be
changed, as warning is not an error or fault.
Bit 8
ms
Manufacturer-specific
Bit 9
rm
Remote
When this bit is ON, the control word is processed. If it is off (local), the control word is not processed.
Bit 10
tr
Target reached
•
ON when the Power drive system has reached the set-point. The set-point is operation mode specific. This Bit
is set to on, if the operation mode has been changed.
•
ON if the quick stop option code is 5, 6, 7 or 8, when the quick stop operation is finished and the Power drive
system is halted.
•
ON when halt occurred and the Power drive system is halted.
Bit 11
ila
Internal limit active
ON when an internal limit is active.
Bit 12 to 13
oms
Operation mode specific
Bit 14 to 15
ms
Manufacturer-specific
Status Word
Power Drive System Finite State Automaton State
xxxx xxxx x0xx 0000 b
Not ready to switch on
xxxx xxxx x1xx 0000 b
Switch on disabled
xxxx xxxx x01x 0001 b
Ready to switch on
xxxx xxxx x01x 0011 b
Switched on
xxxx xxxx x01x 0111 b
Operation enabled
xxxx xxxx x00x 0111 b
Quick stop active
xxxx xxxx x0xx 1111 b
Fault reaction active
xxxx xxxx x0xx 1000 b
Fault
ms
oms
ila
tr
qs
ms
rm
sod
w
oe
so
f
ve
rtso
15 ... 14
13 ... 12
11
10
9
8
0
1
2
3
6
7
4
5
Bit