![Mitsubishi Electric FX3U-1PG Скачать руководство пользователя страница 118](http://html.mh-extra.com/html/mitsubishi-electric/fx3u-1pg/fx3u-1pg_user-manual_238960118.webp)
10 Program Example
10.1 Assignments
112
FX
3U
-1PG User's Manual
10.1
Assignments
10.1.1 I/O assignments
PLC
FX
3U
-1PG
10.1.2 Device assignments
Device No.
Name
Remarks
X000
Error reset
X001
STOP
X002
Forward limit
Use external wiring with NC contacts.
X003
Reverse limit
Use external wiring with NC contacts.
X004
Forward JOG operation
X005
Reverse JOG operation
X006
DOG type mechanical zero return operation start
X007
1-speed positioning operation start
Y000
Stand by display
Terminal name
Description
Remarks
DOG
DOG input of DOG type mechanical zero return
STOP
Deceleration stop input
PG0
Zero point signal is input form the servo amplifier
FP
Forward pulses output
RP
Reverse pulses output
CLR
CLR signal is being output
Device No.
Name
Remarks
M0
Error reset
M1
STOP
M2
Forward limit
M3
Reverse limit
M4
Forward JOG operation
M5
Reverse JOG operation
M6
DOG type mechanical zero return operation start
M7
Relative/absolute address
Relative address specification
M8
1-speed positioning operation start
M9
Interrupt 1-speed positioning operation start
Always OFF
M10
2-speed positioning operation start
Always OFF
M11
External command positioning operation start
Always OFF
M12
Variable speed operation
Always OFF
M13
Interrupt stop operation start
Always OFF
M14
Interrupt 2-speed positioning operation start
Always OFF
M15
Data-set type mechanical zero return operation start
Always OFF
M20
READY
M28
Positioning completion flag
D11, D10
Current address
D21, D20
Current address (pulse converted value)
D31, D30
Current value of operation speed
Содержание FX3U-1PG
Страница 1: ...FX3U 1PG USER S MANUAL ...
Страница 2: ......
Страница 6: ...Safety Precautions Read these precautions before use 4 MEMO ...
Страница 142: ...Appendix C Differences with FX2N 1PG Appendix C 3 Differences in Operation 136 FX3U 1PG User s Manual MEMO ...