15 External FX I/O Device – FNC 70 to FNC 79
15.10 FNC 79 – TO / Write To A Special Function Block
15.10 FNC 79 – TO / Write To A Special Function Block
Outline
This instruction writes data from a PLC to buffer memories (BFM) in a special extension unit/block.
When a large capacity of data is written to buffer memories (BFM) by this instruction, a watchdog timer error may
occur. When splitting the data to be written does not affect the control, use WBFM (FNC279) instruction.
→
For WBFM (FNC279) instruction, refer to Section 31.2.
1. Instruction format
2. Set data
3. Applicable devices
Explanation of function and operation
1. 16-bit operation (TO and TOP)
→
For the common items between FROM instruction and TO instruction, refer to Subsection 15.9.1.
PLC (word device)
→
Special extension unit/block (BFM)
"n"-point 16-bit data starting from
inside a PLC are transferred (written) to "n"-point buffer memories starting
from the buffer memory (BFM) # m2 inside a special extension unit/block No. m1.
Operand Type
Description
Data Type
m1
Unit number of a special extension unit/block
(K0 to K7 from the right side of the main unit)
16- or 32-bit binary
m2
Transfer destination buffer memory (BFM) number
16- or 32-bit binary
Device number storing the transfer source data
16- or 32-bit binary
n
Number of transfer points
16- or 32-bit binary
Oper-
and
Type
Bit Devices
Word Devices
Others
System User
Digit Specification
System User
Special
Unit
Index
Con-
stant
Real
Number
Charac-
ter String
Pointer
X Y M T C S D
.b KnX KnY KnM KnS T C D R U
\G
V
Z Modify K H
E
"
"
P
m1
3 3
3 3
m2
3 3
3 3
3
3
3
3 3 3 3
3 3
3
n
3 3
3 3
P
FNC 79
TO
D
DTO
DTOP
Mnemonic
Operation Condition
32-bit Instruction
17 steps
Continuous
Operation
Pulse (Single)
Operation
16-bit Instruction
9 steps
Mnemonic
Operation Condition
Continuous
Operation
Pulse (Single)
Operation
TO
TOP
S
S
S
Command
input
FNC 79
TO
m1
m2
n
S
Unit No.
m1 = 0 to 7
Transfer destination (Special
extension unit/block) BFM #
m2 = 0 to 32766
Transfer source (PLC)
Number of transfer points
n = 1 to 32767