2.10.1
Connection of Special Adapters
Special adapters of the FX
3U
series can be mounted on the left side of the base unit of the FX
3G,
FX
3U
, and FX
3UC
series.
NOTE
The following rules apply to FX
3U
base units. For the rules of system configuration for the
FX
3G
or FX
3UC
series, please refer to the appropriate manual.
High-speed input/output special adapters
Up to two high-speed input special adapters FX
3U
-4HSX-ADP and up to two high-speed output
special adapters FX
3U
-2HSY-ADP can be connected to a base unit.
Connect all high-speed I/O special adapters before connecting other special adapters when
they are used in combination. A high-speed I/O special adapter can not be mounted on the left
side of a communication or analog special adapter.
When only high-speed input/output special adapters are connected, the adapters can be used
without a communication or interface adapter board installed in the base unit.
Combination of analog and communication special adapters
Analog and communication special adapters must be used with a communication adapter board
or an interface adapter board installed in the base unit.
System Configuration
The Hardware
2 - 36
MITSUBISHI ELECTRIC
Possible
configuration
Communication
special adapter
Analog
special adapter
No communication adapter board
or interface adapter board
Base unit
Communication or
interface adapter
board
Communication
special adapter
Analog
special adapter
Base unit
Illegal
configuration
These adapters do not function.
High-speed I/O
special adapter
Possible
configuration
High-speed I/O
special adapter
High-speed I/O
special adapter
Communication or
interface adapter
board
Base unit
High-speed I/O
special adapter
High-speed I/O
special adapter
High-speed I/O
special adapter
No communication adapter board
or interface adapter board
Base unit
Possible
configuration
Содержание FX2N-32CAN
Страница 1: ...MITSUBISHI ELECTRIC FACTORY AUTOMATION Programmable Logic Controllers GX IEC Developer ...
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 10: ...IV MITSUBISHI ELECTRIC ...
Страница 18: ...Modular PLC Training Hardware Course Overview and Requirements 1 2 MITSUBISHI ELECTRIC ...
Страница 172: ...Monitoring Instances of Function Blocks Advanced Monitoring Functions 7 12 MITSUBISHI ELECTRIC ...
Страница 176: ...Device Edit 8 4 MITSUBISHI ELECTRIC ...
Страница 190: ...Assigning DUT Variables to Function Blocks Data Unit Types DUT 10 10 MITSUBISHI ELECTRIC ...
Страница 198: ...Array Example Single Dimension Array Arrays 11 8 MITSUBISHI ELECTRIC ...
Страница 219: ...Sequential Function Chart SFC SFC Elements Training Manual GX IEC Developer 14 3 ...
Страница 220: ...14 3 SFC configuration examples SFC configuration examples Sequential Function Chart SFC 14 4 MITSUBISHI ELECTRIC ...
Страница 230: ...Structured Text Program Example IEC Structured Text 16 4 MITSUBISHI ELECTRIC ...
Страница 248: ...Configuring GX IEC Developer to access the PLC on Ethernet Ethernet Communications 18 10 MITSUBISHI ELECTRIC ...
Страница 278: ...PLC Components Glossary Appendix A 18 MITSUBISHI ELECTRIC ...
Страница 283: ......