30
3. CONVERSION RULES FOR THE PROGRAM CONVERSION FUNCTION
3.3.2
Additional information on converting master control instructions
MR and MCR master control instructions are converted as shown in the table below.
■
Differences in master control instruction expressions between F
1,
F
1J, and
F
2
programmable con-
trollers and FX series programmable controllers
The table shows the differences in the instruction structure of master control instructions in F
1,
F
1J,
and
F
2
programmable controllers and FX series programmable controllers.
Jump instruc-
tion
CJP
700 to 707
Convert
CJ
PO to P7
The device numbers are
converted from octals to
decimals.
For more information on
conversion, refer to
Chapter 3.3.4.
710 to 717
P8 to P15
720 to 727
P16 to P23
730 to 737
P24 to P31
740 to 747
P32 to P39
750 to 757
P40 to P47
760 to 767
P48 to P55
770 to 776
P56 to P62
777
NOP
-
EJP
700 to 707
PO to P7
710 to 717
P8 to P15
720 to 727
P16 to P23
730 to 737
P24 to P31
740 to 747
P32 to P39
750 to 757
P40 to P47
760 to 767
P48 to P55
770 to 776
P56 to P62
777
NOP
-
Other instructions NOP
-
NOP
-
Termination
instruction
END
-
END
-
Programmable
controller
Instruction
structure
Remarks
F
1
, F
1J
, F
2
OUT, MC, and
MCR instructions
• The OUT instruction runs the MC contact.
• Connect the auxiliary relay specified in the instruction to the ladder block
between the MC and MCR instructions as a shared contact in series.
FX
MC and MCR
instructions
• The MC instruction runs the MC contact.
• Connect the auxiliary relay specified in the instruction to the lad-
der block between the MC and MCR instructions in the same nest
as a shared contact in series.
• The nesting function can be used to set master control instruc-
tions in master control.
F
1
, F
1J
, F
2
FX
Remarks
Instruction
Target device
Instruction Device after conversion