10
1.2.4
Selection of peripheral devices
Check the inverter type of the inverter you purchased. Appropriate peripheral devices
must be selected according to the capacity.
Refer to the following list and prepare appropriate peripheral devices:
1) Three-phase 200V power input
2) Three-phase 400V power input
Motor
Output
(kW)
Applied Inverter
Type
Moulded Case
Circuit Breaker
(MCCB *1, 4) or
Earth Leakage
Circuit Breaker
(ELB) (Refer to
page 12) (*2, 4)
Magnetic
Contactor
(MC)
(Refer to
page 16)
AC Reactor
FR-HAL-
K
FR-BAL-
K
(Refer to page
17)
DC Reactor
FR-HEL-
K
FR-BEL-
K
(Refer to page
17)
0.1
FR-S520E-0.1K(-C)
30AF/5A
S-N10
0.4 (*3)
0.4 (*3)
0.2
FR-S520E-0.2K(-C)
30AF/5A
S-N10
0.4 (*3)
0.4 (*3)
0.4
FR-S520E-0.4K(-C)
30AF/5A
S-N10
0.4
0.4
0.75
FR-S520E-0.75K(-C)
30AF/10A
S-N10
0.75
0.75
1.5
FR-S520E-1.5K(-C)
30AF/15A
S-N10
1.5
1.5
2.2
FR-S520E-2.2K(-C)
30AF/20A
S-N10
2.2
2.2
3.7
FR-S520E-3.7K(-C)
30AF/30A
S-N20,
S-N21
3.7
3.7
Motor
Output
(kW)
Applied Inverter
Type
Moulded Case
Circuit Breaker
(MCCB *1, 4) or
Earth Leakage
Circuit Breaker
(ELB) (Refer to
page 12) (*2, 4)
Magnetic
Contactor
(MC)
(Refer to
page 16)
AC Reactor
FR-HAL-
K
FR-BAL-
K
(Refer to page
17)
DC Reactor
FR-HEL-
K
FR-BEL-
K
(Refer to page
17)
0.4
FR-S540E-0.4K
30AF/5A
S-N10
H0.4
H0.4
0.75
FR-S540E-0.75K
30AF/5A
S-N10
H0.75
H0.75
1.5
FR-S540E-1.5K
30AF/10A
S-N10
H1.5
H1.5
2.2
FR-S540E-2.2K
30AF/15A
S-N10
H2.2
H2.2
3.7
FR-S540E-3.7K
30AF/20A
S-N20,
S-N21
H3.7
H3.7