Installation and wiring
Control circuit
FR-F800
2 - 57
2.6.4 Wiring
precautions
●
It is recommended to use a cable of 0.3 to 0.75 mm² for the connection to the control circuit
terminals.
●
The wiring length should be 30 m (200 m for the terminal FM) at the maximum.
●
Use two or more parallel micro-signal contacts or twin contacts to prevent contact faults when
using contact inputs since the control circuit input signals are micro-currents.
●
To suppress EMI, use shielded or twisted cables for the control circuit terminals and run them away
from the main and power circuits (including the 200 V relay sequence circuit). For the cables
connected to the control circuit terminals, connect their shields to the common terminal of the
connected control circuit terminal. When connecting an external power supply to the terminal
PC, however, connect the shield of the power supply cable to the negative side of the external
power supply. Do not directly earth (ground) the shield to the enclosure, etc.
●
Always apply a voltage to the fault output terminals (A1, B1, C1, A2, B2, C2) via a relay coil, lamp, etc.
●
For the FR-F820-03160(75K) or higher and FR-F840-02160(90K) or higher, separate the wiring of
the control circuit away from the wiring of the main circuit.
Make cuts in rubber bush of the inverter side and lead the wires through.
Fig. 2-37:
Contacts
I001021E
I002375E
Fig. 2-38:
Wiring of the control circuit of the FR-F820-03160(75K) or higher and FR-F840-02160(90K)
or higher
Micro signal contacts
Twin contacts
Rubber bush
(viewed from inside)
Make cuts along the lines on the inside with
a cutter knife.
Wiring example
Содержание FR-F820-00046
Страница 2: ......
Страница 4: ......
Страница 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Страница 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Страница 874: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 900: ...Outline dimension drawings Specifications 8 26 ...
Страница 928: ...EC Declarations of Conformity Appendix A 28 A 6 EC Declarations of Conformity A 6 1 FR F820 FR F840 FR F842 series ...
Страница 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Страница 930: ...EC Declarations of Conformity Appendix A 30 ...
Страница 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Страница 932: ...EC Declarations of Conformity Appendix A 32 ...
Страница 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Страница 934: ...EC Declarations of Conformity Appendix A 34 ...
Страница 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Страница 936: ...EC Declarations of Conformity Appendix A 36 ...
Страница 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Страница 938: ...EC Declarations of Conformity Appendix A 38 ...
Страница 939: ......