Control circuit
Installation and wiring
2 - 46
2.6 Control
circuit
2.6.1
Details on the control circuit terminals
Input signal function of the terminals in
grey shaded fields can be selected by setting Pr. 178
to Pr. 196 (I/O terminal function selection). (Refer to page 5-285.)
Input signal
Ty
p
e
Terminal
symbol
Terminal name
Terminal function description
Rated
specification
Refer
to
page
Co
nt
a
ct
in
p
u
t
STF
Forward rotation
start
Turn ON the STF signal to start
forward rotation and turn it OFF to
stop.
When the STF
and STR signals
are turned ON
simultaneously,
the stop
command is
given.
Input resistance
4.7 k
Ω
Voltage when
contacts are open:
21 to 27 V DC
When contacts are
short-circuited:
4 to 6 mA DC
STR
Reverse rotation
start
Turn ON the STR signal to start
reverse rotation and turn it OFF to
stop.
STP (STOP)
Start self-holding
selection
Turn ON the STP (STOP) signal to self-hold the start
signal.
RH, RM, RL
Multi-speed
selection
Multi-speed can be selected according to the
combination of RH, RM and RL signals.
JOG
Jog mode selection
Turn ON the JOG signal to enable JOG operation
(initial setting) and turn ON the start signal (STF or
STR) to start JOG operation.
Pulse train input
Terminal JOG is also used as a pulse train input
terminal. To use as a pulse train input terminal, change
the Pr. 291 setting. (maximum input pulse: 100k
pulses/s)
Input resistance
2 k
Ω
When contacts are
short-circuited:
8 to 13 mA DC
RT
Second function
selection
Turn ON the RT signal to enable the second function.
When the second function such as "second torque
boost" and "second V/F (base frequency)" is set,
turning ON the RT signal enables the selected
function.
Input resistance
4.7 k
Ω
Voltage when
contacts are open:
21 to 27 V DC
When contacts are
short-circuited:
4 to 6 mA DC
MRS
Output stop
Turn ON the MRS signal (20 ms or more) to stop the
inverter output.
Use this signal to shut off the inverter output when
stopping the motor with an electromagnetic brake.
RES
Reset
Use this signal to reset a fault output provided when a
protective function is activated. Turn ON the RES
signal for 0.1 s or longer, then turn it OFF.
In the initial setting, reset is set always-enabled. By
setting Pr. 75, reset can be set enabled only at fault
occurrence. The inverter recovers about 1 s after the
reset is released.
AU
Terminal 4 input
selection
The terminal 4 function is available only when the AU
signal is turned ON.
Turning the AU signal ON makes terminal 2 invalid.
CS
No function
Use Pr. 186 "CS terminal function selection" for
function assignment.
—
SD
Contact input
common (sink)
Common terminal for the contact input terminal (sink
logic), terminal FM.
⎯
⎯
External transistor
common (source)
Connect this terminal to the power supply common
terminal of a transistor output (open collector output)
device, such as a programmable controller, in the
source logic to avoid malfunction by undesirable
current.
24 V DC power
supply common
Common terminal for the 24 V DC power supply
(terminal PC, te24)
Isolated from terminals 5 and SE.
Tab. 2-18:
Input signals (1)
Содержание FR-F820-00046
Страница 2: ......
Страница 4: ......
Страница 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Страница 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Страница 874: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 900: ...Outline dimension drawings Specifications 8 26 ...
Страница 928: ...EC Declarations of Conformity Appendix A 28 A 6 EC Declarations of Conformity A 6 1 FR F820 FR F840 FR F842 series ...
Страница 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Страница 930: ...EC Declarations of Conformity Appendix A 30 ...
Страница 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Страница 932: ...EC Declarations of Conformity Appendix A 32 ...
Страница 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Страница 934: ...EC Declarations of Conformity Appendix A 34 ...
Страница 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Страница 936: ...EC Declarations of Conformity Appendix A 36 ...
Страница 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Страница 938: ...EC Declarations of Conformity Appendix A 38 ...
Страница 939: ......