![Mitsubishi Electric FR-F820-00046 Скачать руководство пользователя страница 736](http://html.mh-extra.com/html/mitsubishi-electric/fr-f820-00046/fr-f820-00046_instruction-manual_1811886736.webp)
(G) Control parameters
Parameters
5 - 564
5.13.12 Increased
magnetic
excitation deceleration
Increase the loss in the motor by increasing the magnetic flux at the time of deceleration. Decelera-
tion time can be reduced by suppressing the stall prevention (overvoltage) (oL).
It will make possible to reduce the deceleration time without a brake resistor.
Setting of increased magnetic excitation rate (Pr. 660, Pr. 661)
●
To enable the increased magnetic excitation deceleration, set Pr. 660 "Increased magnetic excita-
tion deceleration operation selection" = "1".
●
Set the amount of excitation increase in Pr. 661 "Magnetic excitation increase rate". Increased
magnetic excitation deceleration will be disabled when Pr. 661 = "0".
●
When the DC bus voltage exceeds the increased magnetic excitation deceleration operation level
during the deceleration, excitation is increased in accordance with the setting value in Pr. 661.
●
The increased magnetic excitation deceleration will continue even if the DC bus voltage goes
under the increased magnetic excitation deceleration operation level during strengthened ex-
citation deceleration.
●
When the stall prevention (overvoltage) occurs during the increased magnetic excitation decel-
eration operation, increase the deceleration time or raise the setting value of Pr. 661. When the
stall prevention (overcurrent) occurs, increase the deceleration time or lower the setting value of
Pr. 661.
●
Increased magnetic excitation deceleration is enabled with V/F control, Advanced magnetic flux
vector control.
Pr.
Name
Initial
value
Setting
range
Description
660
G130
Increased magnetic
excitation deceleration
operation selection
0
0
Without increased magnetic excitation deceleration
1
With increased magnetic excitation deceleration
661
G131
Magnetic excitation
increase rate
9999
0 to 40%
Set the increase of excitation.
9999
Magnetic excitation increase rate 10%
662
G132
Increased magnetic
excitation current level
100%
0 to 300%
The increased magnetic excitation rate is
automatically lowered when the output current
exceeds the setting value at the time of increased
magnetic excitation deceleration.
Inverter
Increased magnetic excitation deceleration operation level
200 V class
340 V
400 V class
680 V
With 500 V input
740 V
Tab. 5-288:
Strengthened excitation deceleration operation level
NOTE
The increased magnetic excitation deceleration will be disabled in the following conditions:
During PM motor control, power failure stop, operation with FR-HC2/FR-CV, energy saving opera-
tion, Optimum excitation control.
V/F
V/F
V/F
Magnetic flux
Magnetic flux
Magnetic flux
Содержание FR-F820-00046
Страница 2: ......
Страница 4: ......
Страница 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Страница 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Страница 874: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 900: ...Outline dimension drawings Specifications 8 26 ...
Страница 928: ...EC Declarations of Conformity Appendix A 28 A 6 EC Declarations of Conformity A 6 1 FR F820 FR F840 FR F842 series ...
Страница 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Страница 930: ...EC Declarations of Conformity Appendix A 30 ...
Страница 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Страница 932: ...EC Declarations of Conformity Appendix A 32 ...
Страница 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Страница 934: ...EC Declarations of Conformity Appendix A 34 ...