Pr.
Name
Initial
value
Setting range
Description
1361
A440
Detection time for PID
output hold
5 s
0 to 900 s
Set the time from when the deviation falls within the
PID output hold range until the PID output is held.
1362
A441
PID output hold range
9999
0 to 50%
Set the range in which the PID output is held.
9999
The PID output holding is disabled.
1363
A447
PID Priming time
9999
0 to 360 s
Set the time from when the priming operation starts
until the main pump starts.
9999
The PID priming pump function is disabled.
1364
A448
Stirring time during sleep
15 s
0 to 3600 s
Set the stirring time.
1365
A449
Stirring interval time
0 h
0 to 1000 h
Set the interval time for the stirring operation.
1366
A627
Sleep boost level
9999
0 to 100%
Increase the set point before the PID output
suspension function is activated.
9999
The PID sleep boost function is disabled.
1367
A628
Sleep boost waiting time
0 s
0 to 360 s
Set the waiting time for the sleep boost operation.
1368
A629
Output interruption
cancel time
0 s
0 to 360 s
Set the time from when the deviation reaches the
output interruption cancel level until the output is
started.
111
F031
Check valve deceleration
time
9999
0 to 3600 s
Set the deceleration time for the check valve
deceleration function.
9999
The check valve deceleration function is disabled.
1369
A446
Check valve closing
completion frequency
9999
0 to 120 Hz
Set the frequency at which the check valve
deceleration stops.
9999
The check valve deceleration function is disabled.
1370
A442
Detection time for PID
limiting operation
0 s
0 to 900 s
Set the time from when the measured value input
exceeds the Pr.131 or Pr.132 setting until the FUP or
FDN signal is output.
1371
A443
PID upper/lower limit pre-
warning level range
9999
0 to 50%
Set the operation range for the PID upper/lower limit
pre-warning function.
9999
The PID upper/lower limit pre-warning function is
disabled.
1372
A444
PID measured value
control set point change
amount
5%
0 to 50%
Set the set point change amount for the PID upper/
lower limit pre-warning operation.
1373
A445
PID measured value
control set point change
rate
0%
0 to 100%
Set the set point change rate for the PID upper/lower
limit pre-warning operation.
1374
A450
Auxiliary pressure pump
operation starting level
1000%
900 to 1100%
Set the deviation level for operating the auxiliary
pressure pump.
1375
A451
Auxiliary pressure pump
operation stopping level
1000%
900 to 1100%
Set the deviation level for stopping the auxiliary
pressure pump.
1376
A414
Auxiliary motor stopping
level
9999
0 to 100%
Set the level for stopping the auxiliary motor by the
PID overpressure control function.
9999
The PID overpressure control function is disabled.
1377
A452
PID input pressure
selection
9999
1
Terminal 1 pressure input
2
Terminal 2 pressure input
3
Terminal 4 pressure input
9999
The PID input pressure control function is disabled.
1378
A453
PID input pressure
warning level
20%
0 to 100%
Set the input pressure warning level.
1379
A454
PID input pressure fault
level
9999
0 to 100%
Set the input pressure fault level.
9999
The input pressure fault detection is disabled.
Содержание FR-F820-00046
Страница 2: ......
Страница 4: ......
Страница 114: ...System configuration for Ethernet communication FR F800 E Installation and wiring 2 86 ...
Страница 172: ...Basic operation procedure JOG operation Basic operation 4 32 ...
Страница 812: ...Inverter to inverter link function FR F800 E Parameters 5 640 ...
Страница 874: ...Measurement of main circuit voltages currents and powers Precautions for maintenance and inspection 7 20 ...
Страница 900: ...Outline dimension drawings Specifications 8 26 ...
Страница 928: ...EC Declarations of Conformity Appendix A 28 A 6 EC Declarations of Conformity A 6 1 FR F820 FR F840 FR F842 series ...
Страница 929: ...Appendix EC Declarations of Conformity FR F800 A 29 ...
Страница 930: ...EC Declarations of Conformity Appendix A 30 ...
Страница 931: ...Appendix EC Declarations of Conformity FR F800 A 31 ...
Страница 932: ...EC Declarations of Conformity Appendix A 32 ...
Страница 933: ...Appendix EC Declarations of Conformity FR F800 A 33 ...
Страница 934: ...EC Declarations of Conformity Appendix A 34 ...
Страница 935: ...Appendix EC Declarations of Conformity FR F800 A 35 ...
Страница 936: ...EC Declarations of Conformity Appendix A 36 ...
Страница 937: ...Appendix EC Declarations of Conformity FR F800 A 37 ...
Страница 938: ...EC Declarations of Conformity Appendix A 38 ...
Страница 939: ......